Conventional Mode or Conventional DHA Device
To activate the conventional mode, with the jumper removed, enter the address 0 in the dip switch.
Insert the battery jumper.
The Green and Red LEDs start to flash simultaneously.
Connect the DHA to 24V on the (LOOP in) plug. After this step, the DHA will report the status of the door and battery charge through the LEDs
indicated in the table below.
If by order of a conventional panel or other device the 24V fails, the DHA will release the door in a maximum time of 3 seconds.
At the insistence to re-open the door and dock at the DHA it will continually release it within three seconds.
After the 24V failure the DHA will monitor the door, but if there is no activity to dock it back to the DHA, it will go into sleep mode after 30 minutes
to protect the battery charge. The DHA will wake up automatically after the 24V returns to the system.
The DHA, after the port is docked, monitors its status every 100 seconds, if for any reason the door is released without an order from the release
button, the DHA will, in the case of the conventional system, return information that the door is released in the LEDs status.
REPORTING DETAILS (Conventional Mode)
LED SYSTEM REPORTING STATUS
CAUSE / BEHAVIOUR
Continuous
Blinking
---
Battery charge OK. Charging system OFF.
The door is open (attached in the magnet).
---
Battery charging.
The door is open (attached in the magnet).
Blinks every 2,5 seconds
Battery charge OK. Charging system OFF.
The door is closed (not attached to the magnet).
The Red LED blinks every 2,5 seconds
the Green every ¼ of second
Battery charging.
The door is closed (not attached to the magnet).
---
The Red and Green LEDs blinks
every ¼ of seconds
Jumper removed or battery missing.
---
---
Module off or in sleep mode.
LOOP CONNECTIONS
Maximum number of devices between 2 Isolators: 32 (EN54-2) - 20 (BS5839)