5
briefly. If the sent value is equal to or above the set parame
-
ter, the LED lights flickers for 2 s.
The following control commands can be triggered
with the remote control:
Control command
Description
Can be trigge-
red by app
Teach-in channel A
Activation
x
Switching light
Lighting group can be switched on
and off.
x
Presence test
On/Off
x
Restart
Restart detector
x
Factory settings
Set all parameters and settings to
factory setting.
x
Detection zone
The detection area is divided into two independent detection
zones (see 5. Detection area). For a maximum range, zone 1
and zone 2 are activated. If a limitation of the detection area
is required, zone 1 or zone 2 can be deactivated.
Value range (Glamox Sensor-app)
Selection of detection area
Z1, Z2, Z1 and Z2
Brightness setpoint channel A light
Brightness setpoint A defines the minimum desired bright
-
ness. The currently prevailing brightness is measured under
-
neath the presence detector. If the prevailing brightness is
below the setpoint value, the light is switched on when a
presence is detected (in configuration type fully automatic
device).
Value range (Glamox Sensor-app)
Min. brightness setpoint value
30–3000 Lux
Deactivation of brightness measurement (brightness
measurement has no effect)
The lighting channels only switch according to presence
and absence.
Measurement off
Teach-in channel A light
During teach-in, the currently measured brightness value is
accepted as brightness setpoint value A. Values outside the
permitted range will automatically be set to the appropriate
limit value.
Value range (Glamox Sensor-app)
Teach-in channel A
Teach-in for channel A light
Brightness actual value A
The brightness actual value can be checked for monitoring
purposes. To check, see the „Parameters ans commands via
remote control“ table.
Room correction factor lighting A, Brightness
measurement value lighting A
The room correction factor is a measure of the different
brightness measurements at the ceiling and on the work
surface (the brightness value depends on the ambient
conditions).
Room correction factor = Brightness value at the ceiling
Brightness value on the floor
The brightness measurement value at the ceiling is influenced
by the installation location, incidence of light, position of the
sun, weather conditions, the reflection properties of the room,
and the furniture. In order to be able to adhere to the requi
-
red lux value in the desired area, a comparison of the bright-
ness measurements is necessary.
The measured lux meter value
below the presence detector
is sent to the detector via the remote control.
When sending the brightness measurement value, the room
correction factor of the corresponding lighting channel is
automatically adjusted to the conditions inside the room.
Two different procedures can be selected in the app for the
comparison (automatic/manual calibration).
¾
Connect the app remote control LMS MG PROGRAM
REMOTE BT with the corresponding Glamox Sensor-app.
¾
Select the appropriate detector type <LMS MG PIR CLS
SENSOR-R LONG> and load the parameter set.
¾
Select the <Brightness measurement value A> parameter.
Automatic calibration
¾
Set up the LMS MG PROGRAM REMOTE BT according to
the drawing, and move a few steps away from the mea-
surement location, so the lux measurement will not be
influenced.
¾
Press OK.
▻
A new window with the measured brightness measu-
rement value is shown. If you would like to apply this
value,
¾
Press OK.
¾
Important
: Press the send button (
). After this, the
brightness measurement is calibrated.
Manuel calibration using the lux meter
¾
Set up or align the lux meter according to the drawing, and
read the lux value.
¾
Press „Enter“ in the app.
▻ A new window opens.
¾
Enter the lux value and press OK.
▻
The brightness measurement value appears in the
display.
¾
Important
: Press the send button (
). After this, the
brightness measurement is calibrated.
•
The calculated room correction factor is adopted. The
room correction factor can be checked via the <Room
correction factor A> parameter for monitoring purposes.
The default value is 0.3.