PROGRAMMING

To change any of the MX20 settings, change the configuration 

of the programming switches (see Figure 9) as required, 

switch 4 controls LED state, switch 3 controls Pulse Count and 

switches 1 and 2 control range. 

Example: To change the range to 10 metres: 

1. Set switch 1 to OFF (down position)

2. Set switch 2 to ON (up position)

PROGRAMMING CHART

Option

Switch Configuration

Reference

LED ON

Switch 4: On (up)

Figure 10

LED OFF

Switch 4: Off (Down)

Figure 11

Pulse 

Count 1 

Switch 3: Off (Down)

Figure 12

Pulse 

Count 2

Switch 3: On (Up)

Figure 13

5 Metre 

Range

Switch 2: Off (Down)

Switch 1: Off (Down)

Figure 14

10 Metre 

Range

Switch 2: On (Up)

Switch 1: Off (Down)

Figure 15

15 Metre 

Range

Switch 2: Off (Down)

Switch 1: On (Up)

Figure 16

20 Metre 

Range

Switch 2: On (Up)

Switch 1: On (Up)

Figure 17

PROGRAMMING OPTIONS DEFINITIONS

Pulse Count 

This is the number of times the unit has to detect on both of its 

sensors before signalling an output

LED 

LED Off  - LED disabled 

LED On - LED signals a detection

WALK TEST

Note: It is recommended that the detection LED be enabled 

during walk test to aid in set up. The detection LED lights each 

time the MX20 detects your presence. 

Note: When you conduct a walk test, make sure that the front 

cover is in place. Do not conduct walk tests with the cover 

removed. 

The range of the detector increases without the protective front 

cover. Therefore the front cover must be fitted to establish the 

correct beam pattern. Use programming chart to adjust the 

range as necessary. Pan and tilt the lens module over the field 

of view to obtain the correct coverage area.

Detection Area

Programmable between 5 & 20 

metres

Coverage

90° detection angle, 20m x 20m 

coverage max

Adjustment

180° pan + 90° tilt

Fresnel Lens

10 zones for each Pyro pair, which 

can be masked with curtain sliders 

ans special masking tape (supplied)

Customised optics

Double silicon shielded quad 

elements eliminates 50,000 lux of 

white light

Outputs

Silent solid state magnetically 

immune

No.1

N/OPEN

Volt free relay signal contact

24V AC/DC @50mA with an integral 

25Ώ resistor

No.2

N/CLOSED

Volt free relay signal contact 

24V AC/DC @ 50mA with an integral 

25Ώ resistor

Alarm 5 seconds

T

Tamper

Volt free, normally closed switch 

output 12VDc @ 25mA

Tamper Switches

Front and rear tamper switches; 

case open and removal from wall

Pulse Count

1 -2

Power Input

9 - 15V dc

Current

8mA (12V nominal)

Operating Temp.

-20°C to +55°C

Conformal coated electronics for 

increased stability

Housing

High Impact ABS

Protection Rating

IP55

Dimensions

84 x 106 x 72mm

Mounting Height

Variable - optimum height 3 metres

CE Mark