The GJD Emerald is a dual area security lighting controller
which enables external areas to be accurately monitored.
It automatically switches up to 3000 Watts of resistive
lighting at night for a pre-set period and can be manually
overridden when required. The controller incorporates an
audible warning tone and features six detector indicators
which illuminate when activated by detection day and night.
OPERATING INSTRUCTIONS
When a detector is activated day or night the relevant
detector indicator flickers and will remain on for the length
of the timer setting. During darkness the lighting will be
switched on automatically while the detector is receiving
activation signals, and will automatically turn off after the
pre-set timer period.
The ‘Zone 1’ and ‘Zone 2’ green indicator have to be
selected for automatically controlled lighting on detection
during darkness.
ZONE 1
ZONE 1
ZONE 1
Green indicator is ‘on’. This mode
must be selected for automatic
lighting during darkness.
Indicator ‘off’. Lighting and tone
are switch off for this zone.
Green indicator flashing. A
detector has activated the
lighting.
Manually selecting this yellow
indicator will turn the lighting
‘on’. Turning the indicator ‘off’ will
return to automatic mode.
Indicator ‘off’.
Yellow indicator flashing. A
detection has automatically
activated the lighting.
Red indicator ‘on’. Audible
warning tone selected. Zone 1
and/or Zone 2 indicator to be
selected to function.
Indicator ‘off’ Audible warning
tone is switched off.
ADJUSTMENT TO FACTORY SETTINGS
When connecting the unit to the electrical supply or when
the supply is interrupted, the indicators will flash for one
minute whilst the system settles. Pressing any button
during this time will start normal operation.
Internal adjustments panel
The factory settings are shown.
AUX - Auxiliary Output (50mA maximum)
OFF -
Internal sounder and auxiliary output disabled
STD -
Internal sounder and auxiliary output active and will
emit a warning tone on each detection when the tone
button is selected.
10-30 Seconds -
The auxiliary output time after last
detection. The internal sounder is as the STD
LIGHT ON TIME IN MINUTES
1 to 24 minutes -
The length of the time after last detection
during darkness. The red detector indicators will stay on for
this time after the last detection day and night.
Pulse Count / Walk Test -
Select the symbol to assist in
location/alignment of the detector beams during daylight
installations. When the detector beams are activated the
external lights will stay on for a period of 6 seconds.
1,2 or 3 -
After completing the ‘walk test’ function, set
the pulse count to the required level. The pulse count is
the number of detector beams that have to be crossed to
trigger the system.
1.
will give fast response
2.
gives better immunity with good response
3.
gives highest immunity to false activation in poor
environments but is less responsive.
OFF
STD
10
20
30
1
3
5
10
24
1
2
3
AUX
TIME SECS
LIGHT ON
TIME MINS
PULSE
COUNT
Emerald 3000 MK3
GJD010 Lighting Controller
Detect
.
Illuminate
.
Deter