background image

-

1

-

04111

D-Tect 2

GJD300 Quad PIR Movement Detector

Package Contents

Package Contains:

1 x D-Tect 2

1 x Drilling template for fixing holes

1 x Allen Key

3 x 31.75mm wall plugs

3 x 31.75mm screws

2 x Spare Sliding Curtains

2 x Tamper Feet

1 x Tamper Cup

1 x Installation manual

Introduction

The D-Tect 2 is an outdoor motion detector and alarm 

trigger that uses two independent passive infra-red 

detectors, both of which must trigger to cause the detector 

to signal an alarm. Utilising quad PIR technology, the D-Tect 

2 delivers precise, reliable presence detection.

3. Feed standard eight-core alarm cable into the 

cable entry. Bare the wires and connect to the top 

PCB terminal block. See Figures 2, 4 & 5.

4. Screw the unit to the wall ensuring that the rear 

tamper pin is correctly located and that the tamper 

microswitch is closed. See Figure 6.
To aid installation, two spare tamper feet are 

provided. One is 1mm longer and the other is 2mm 

longer than the tamper foot originally fitted. The 

tamper foot is a push fit and can be removed by 

carefully pulling it from the pin. See Figure 2.

5. When the detector is aligned, connected, and 

programmed to suit the installation, replace the 

front cover and lock as shown.  See Figure 7.

The multifunction lens fitted to D-Tect 2 produces seven 

long range beams and seven medium to short range curtain 

PIR beams. The PIR circuitry detects changes in heat and 

movement in the beam pattern; therefore items such as 

trees, shrubs, ponds, boiler flues, and animals should be 

considered when positioning the detector. 

Note: 

The PIR sensor is more sensitive to movement 

across the beams, and less sensitive to movement directly 

towards or away from the beams. 

The detector module is fitted with two sliding shutters to 

reduce the detection angle. 

The curtains are fitted to the pan and tilt module as shown 

in Figure 9 (shown with primary and additional curtain 

sliders fitted). Each section of the detector lens gives a 

coverage pattern of approximately 10 degrees. 

An additional set of curtain sliders is provided should the 

beam pattern need to be narrowed even further, e.g. if the 

minimum detection angle of 10 degrees is required. 

When coverage exceeds the desired detection area, adjust 

the module as required and mask off any beams, either 

vertically or horizontally, to avoid unwanted detection. 

Quick Installation

1. Mount and connect the detector following the 

instructions given later in this sheet. 

2. Apply supply voltage to the unit. The detection LED 

(blue) flashes three times. 

3. Wait approximately 2 to 3 minutes to allow the 

detector to settle. 

4. Press the programming button once to activate 

walk test mode. The detection LED is now enabled 

for five minutes. 

Note: The front cover must be fitted when walk 
testing. 

The default settings are: 

Range: 20 meters

Pulse count: 1 (always set to 1 during walk test)

Detection LED: off (always enabled during Walk 

Test)

'S' Lux Level: 5

Contacts:

Alarm 1: Normally Closed

Alarm 2: Normally Open

Contacts Timer: 5 (seconds)

Mounting The Unit

Multibeam Alignment & Masking

During installation, protect the electronics against water, as 

trapped moisture can affect or damage the unit. 

1. Drill the wall to accept the two fixing screws, the 

cable entry, and the tamper cup (if used). See 

Figures 1 and 2. 
A hole-drilling template is provided. 

Note: We recommend using the tamper cup on 
uneven wall surfaces. 

2. Remove the cover assembly by loosening the 

locking screw using the allen key provided.  The 

cover hinges from the top and lifts out of the 

location slot. See Figure 3. 

The D-Tect 2 includes jumpers that allow you to configure 

the internal end-of-line resistor values, when EOL resistors 

are required.  Values are 1K, 2K2, 3K3, 4K7, 5K6 and 6K8 

Ω.  Figure 8 shows:

1. EOL resistor jumpers
2. Wiring points

Alternatively, you can remove the jumpers and connect a 

discrete resistor directly to the alarm or tamper outputs, as 

specified by the third-party equipment.

Connections

Connecting The Unit

Terminal

Label

Description

1

A

24 hour -VE Output

2

S

Dark -VE Output

3, 4

ALARM 1

Alarm relay 1

4, 5

EOL

End-of-line resistors

5, 6

TAMPER N/C

Tamper relay, normally closed

7, 8

ALARM 2

Alarm relay 2

9, 10

9 -24V

AC / DC Supply

Summary of Contents for D-TECT 2 GJD300

Page 1: ...y 10 degrees An additional set of curtain sliders is provided should the beam pattern need to be narrowed even further e g if the minimum detection angle of 10 degrees is required When coverage exceed...

Page 2: ...e D Tect 2 s non volatile memory Note When power is applied to the D Tect 2 the user has a time slot of 5 minutes to start using the IR key fob This can be reset either by pushing the program button a...

Page 3: ...se Count 1 3 Temp Compensation Digital sensitivity adjustment Control Digital microprocessor non volatile memory Walk Test Output test mode with LED indication Operating Temp 20 to 55 Centigrade Confo...

Page 4: ...Template 2 3 4 5 6 Normally Closed Tamper Circuit Front Rear 0V Supply To GJD Lighting Controller 12VDC Supply Alarm Output 1 Multiplexer PTZ Dome DVR Etc Alarm Output 2 Multiplexer PTZ Dome DVR Etc 7...

Page 5: ...5 04111 11 12 13 14 15 16 17 Programming Button Programming LED...

Page 6: ...Notes GJD Manufacturing Limited Unit 2 Birch Industrial Estate Whittle Lane Heywood Lancashire OL10 2SX Sales 44 0 1706 363 998 Technical 44 0 1706 363 990 Fax 44 0 1706 363 991 Email info gjd co uk...

Page 7: ...Notes GJD Manufacturing Limited Unit 2 Birch Industrial Estate Whittle Lane Heywood Lancashire OL10 2SX Sales 44 0 1706 363 998 Technical 44 0 1706 363 990 Fax 44 0 1706 363 991 Email info gjd co uk...

Page 8: ...Notes GJD Manufacturing Limited Unit 2 Birch Industrial Estate Whittle Lane Heywood Lancashire OL10 2SX Sales 44 0 1706 363 998 Technical 44 0 1706 363 990 Fax 44 0 1706 363 991 Email info gjd co uk...

Reviews: