Smoke Detector 

Installation Instructions 

 

 

Smoke Detector 

01/98 

Page: 2 of 5 

Unsuitable Locations 

Never

 install the smoke detector 

  near to air ducting and strong drafts 

  directly in the apex of pitched roofs (a minimum distance of 30 cm from the apex must be 

maintained) 

  in rooms where there is a lot of steam, dust or smoke under normal conditions(e.g. workshops, 

kitchens, bathrooms, laundry rooms, etc.)  

  in rooms where the temperature rises above + 40°C or falls below + 5°C. 

 

 

 
Fig. 1: Locations for installing smoke detectors 

 
 
 
 
 
 

 Minimum 

 protection 
 
 

 Recommended 

 

 

60

80

80

40

Ø 4,0

 

 
Fig. 2: Dimensions 

 
 
 

Installation and Commissioning 

 

  Remove the smoke detector from ist base 

by turning it anticlockwise. 

  Screw the base to the ceiling using the fixing 

materials provided (see Fig. 2 for 
dimensions). 

  Attach the 9 V rectangular battery to the 

connector. 

  Insert the smoke detector into the base and 

turn it gently clockwise until it clicks into 
place. 

 
 

 

Linking Several Smoke Detectors 

With the type Relay/Networking smoke detector up to 40 devices can be linked together in one 
network. To do this, first remove the plastic protection from the terminal strips. The connection from 
detector to detector is by means of a two-core cable (telephone cable), the terminals 3 and 4 (green) 
being used as whown in Fig. 3. An external alarm device can be connected to the volt-free contacts 
via terminals 1 and 2 (orange). 
If an inductive load (e.g. a klexon or a relay of an unknown design) is connected, a free-wheeling 
diode (type 1N4007) must be included in the circuit, so that the smoke detector is not damaged by 
inductive voltages. 
 