Figure 6: Connection diagram for insert with mechanical extension
The insert can only be operated with a mechanical extension if the insert and the extension are
supplied by the same power supply unit. The insert and extension then have the same "-"
potential, and it is sufficient to connect the "+" potential via the extension.
If the extension is supplied via another power supply unit, an additional 24 V insert (10) must be
used that connects both extension inputs.
Figure 7: Connection diagram for two inserts supplied via two power supply units
o
Connect extension according to connection diagram (Figure 5), (Figure 6) or (Figure 7).
Installing the sensor cable
for covers with sensor evaluation
i
The sensor cable carries safety extra-low voltage (SELV). Observe fitting instructions
according to VDE 0100.
The sensor cable can be installed in three different ways. In-wall routing (Figure 8), surface-
mounted routing (Figure 9), and with appropriate covers plugging the sensor cable into the
cover (Figure 11).
32545312
10499098 I00
17.05.2011
5/8
Blind control system
Blind controller insert DC 24 V