7014 WASTE LIQUID
LEVEL SENSOR
Bevel required
46mm A/F
O-ring
watertight seal
1.25” BSP Thread
To use the O-ring seal, the mounting hole requires a 3mm x 45° bevel
around the upper edge of the hole. Fit the sensor into a
1.25” BSP
threaded hole using a 46mm A/F spanner. Tighten to 50Nm torque
ensuring the flange face is flush to the top of the tank.
Ensure gasket is centered
under the sensor flange
Using 46mm spanner
tighten to 50Nm
If it is not possible
to create a bevel, then the gasket should be used.
Remove the O-ring and fit the gasket over the thread mount, black side
up. Ensure the gasket is centered under the sensor and tighten to a
torque of 50Nm.
Floor panels
Clearance
when
installed
Require 90mm minimum
clearance to allow for
bend of cable
Once installed the sensor requires
a minimum of 90mm from the top of
the tank to the underside of the housing to allow for cable bend.
45° max
.
The sensor can be installed
at any angle from vertical to a maximum
recommended angle of 45°. Even at its maximum supplied length of 2
metres the sensor does not require any supports inside the tank.
Analogue Output options are as follows:
RED
= Power
BLACK
= Ground
WHITE
= Measurement
BLUE
= Switch
BARE
= Shield
Indicator =
Gauge =
The sensor requires a DC power supply between 6V and 32V. It has
reverse polarity protection to -32V and over voltage protection to +/- 50V
(5 minutes).