Page 6-1
Required Equipment
Troubleshooting and Analysis
MDE-5394B VaporTEK™/VaporTEK-3 Controller Board 110 V UL® Vapor Recovery Collection System for Encore® 500 S
Start-Up and Service Manual · March 2019
6 – Troubleshooting and Analysis
Required Equipment
The following equipment is required for troubleshooting and analysis:
Description
Part Number
Burkert Flow Meter with Elaflex-style Nozzle Adapter, and Rubber Hose
between Adapter and Meter
M13351A001
FB1 Handheld Terminal (includes 15-pin to RS-422 cable supplied with unit)
M13353A001
VaporTEK-Universal Serial Bus (USB) Flash Adapter Interface (Isolated)
141057636
Nozzle Adapter to collect vapor (varies with nozzle manufacturer) for Gilbarco
Veeder-Root AVRN/ICVN and OPW 12VW
Note: Only the correct adapter can be used for system calibration.
579290-001
Troubleshooting Tools
The following tool is available for advanced troubleshooting and analysis:
• VaporTEK Programming software (refer to
)
VaporTEK Software
By connecting a laptop with a terminal emulator (HyperTerminal or equivalent) to the
computer on the VaporTEK “PROGRAM” Connector, a site technician can access all the setup
parameters and view enhanced service information from VaporTEK-3 Controller Board in real
time.
Note: Shut down the 115 V AC Main power to the VaporTEK Controller Board and wait at
least 30 seconds for power down before the flash adapter can be plugged into the
PROGRAM-Connector. Check the LED V1 and V6 to ensure that the power is down.
Do not touch any board components if main power is ON.
Use only this special isolated USB Adapter to connect the laptop to the VaporTEK-3
Controller Board. P/N: 141 057 636 (see
WARNING