Page 5-7
Pulse Rate Setup with FB1 Terminal
VaporTEK Calibration Start-up Sequence
MDE-5394B VaporTEK™/VaporTEK-3 Controller Board 110 V UL® Vapor Recovery Collection System for Encore® 500 S
Start-Up and Service Manual · March 2019
Pulse Rate Setup with FB1 Terminal
Pulse Rate Setup on VaporTEK Controller
The VaporTEK interface receives pulses from an active encoder and calculates the current
flow rate by using adjusted pulse rate - Range: 50 to 200 pulses/liter
(1 U.S. Gallon = 3.785 liters). The pulse rate for a VaporTEK interface should be set to 136
pulses/liter for Encore 500 S.
If the dispenser is running, the FB1 terminal will show the current petrol flow rate on the
FB1’s display by using the FB1 - Sub menu item “Fuel flow (3)” (see step
on
).
You need to use the procedure explained in
rate is 136 pulses/liter. It cannot be set to any other number on an Encore dispenser.
The pulse rate adjustment can be set up either using the FB1 service terminal connected to the
VaporTEK interface or a laptop connected to the VaporTEK interface.
Pulse Rate Setup with FB1
To set up the pulse rate on the FB1 terminal, proceed as follows:
1
Switch on the FB1. Wait until the menu shown in
1
.
Figure 5-8: Pulse Rate Setup - Screen 1
2
When the screen shown in
opens, press
2
.
Figure 5-9: Pulse Rate Setup - Screen 2