VaporTEK Calibration Start-up Sequence
External Flow Meter Calibration
Page 5-6
MDE-5394B VaporTEK™/VaporTEK-3 Controller Board 110 V UL® Vapor Recovery Collection System for Encore® 500 S
Start-Up and Service Manual · March 2019
3
Press
F5
when the following screen opens.
Figure 5-4: Gas Meter Calibration - Screen 3
4
Match the Calib. factor (calibration factor) on the gas meter (see
) with the
following display on the FB1 terminal (see
). If the calibration factor already
matches, press
ENTER
. If not, press
F2
to change the calibration factor.
Figure 5-5: Gas Meter Calibration - Screen 4
5
Enter the Calib. factor (calibration factor) shown on the gas meter and press
Enter
when the
following screen opens (for example, 07 is now the new factor).
Figure 5-6: Gas Meter Calibration - Screen 5
Figure 5-7: Burkert Gas Meter Calibration Factor
K-factor