Page 5-3
Programming Pump 02.8.86 or Later for Collection Only
VaporTEK Calibration Start-up Sequence
MDE-5394B VaporTEK™/VaporTEK-3 Controller Board 110 V UL® Vapor Recovery Collection System for Encore® 500 S
Start-Up and Service Manual · March 2019
Programming Dispenser
After accessing the dispenser for programming, proceed as follows:
1
Press
F1
on the manager keypad.
2
Press
0
>
1
>
2
>
8
>
Enter
(display flashes 0000).
3
Press
91
>
Enter
(top right-side digit blinks).
4
Press
4
>
Enter
(right digit in cash).
Note: The VaporTEK error codes work correctly only if CC 91 is set to 4.
5
Turn Electronic Calibration (ECAL) switch to right.
6
Press
1
>
Enter
(for vapor collection only, Monitoring system is not installed).
7
Press
F1
. The VaporVac is now set for vapor collection only.
Next, the fuel density must be programmed:
8
Press
75
>
Enter
.
9
Press
1
>
Enter
(for meter 1), volume blinks.
10
Press
1
>
Enter
(for gas).
11
Press
2
>
Enter
(for meter 2), right-side cash blinks.
12
Press
1 > Enter
(for gas), volume blinks.
13
Press
5
>
Enter
(for meter 5), right-side cash blinks.
14
Press
1
>
Enter
(for gas), volume blinks.
15
Press
6
>
Enter
(for meter 6), right-side cash blinks.
16
Press
1
>
Enter
(for gas), volume blinks.
If unit is a three-grade, you must program meters 3 and 4. If this is a two-grade unit, proceed to
step
.
17
Press
3
>
Enter
(for meter 3), right-side cash blinks.
18
Press
1
>
Enter
(1 for gas/2 for diesel), volume blinks.
19
Press
4
>
Enter
(for meter 4), right-side cash blinks.
20
Press
1
>
Enter
(1 for gas/2 for diesel), volume blinks.
21
Return ECAL switch to left.
22
Press
F2
to return to idle state.