VaporTEK Calibration Start-up Sequence
Programming Pump 02.8.86 or Later for Collection Only
Page 5-2
MDE-5394B VaporTEK™/VaporTEK-3 Controller Board 110 V UL® Vapor Recovery Collection System for Encore® 500 S
Start-Up and Service Manual · March 2019
Programming Pump 02.8.86 or Later for Collection Only
• Windows XP
®
has HyperTerminal resident on the computer. For any laptop system
newer than Windows XP, use M16 Flasher.
• For dispenser/pump programming, refer to
MDE-3804 Encore and Eclipse
Start-up/Service Manual
.
IMPORTANT INFORMATION
Error Codes
The following table lists the error codes associated with VaporTEK:
Error Code
Description
6042
Vaporix alarm side A.
6043
Vaporix alarm side B.
6044
Vaporix option is set, but board is not detected.
6045
Shutdown warning side A (show on the dispenser log file).
6046
Shutdown warning side B (show on the dispenser log file).
6047
Vaporix board is detected, but option is not set.
Vapor recovery units require two special programming steps. First, the PCN must be set up to
provide output pulses to the VaporTEK interface using Command Code (
CC
)
91
, Function
Code (
FC
)
3
. Then, the fuel density must be set using
CC
75
.
Accessing Dispenser Programming
To gain access to dispenser programming and bypass the dispenser security feature, proceed as
follows:
1
Disconnect the two-wire communication cable from the pump node at P1109.
2
Cycle power to the dispenser and wait for five minutes after unit has completely booted up.
3
Press
F1
on the manager keypad. If you get a double beep when pressing F1, then you need to
wait longer. If the double beep continues even after eight minutes, verify step
and perform
step
again. Once successful, the main display will be flashing 8888 after F1 is pressed.