TIMES LEARNING PROCEDURE
1. When the door is closet, place the DIP n°1 (DIP SWITCH DIP1) on ON. The yellow LED DL5 flashes fast.
In this phase, if the DIP n°1 is put on OFF you leave the procedure, the memorized data remain stored and the
next START command will cause the opening.
2. START
→
The motor moves in opening. The yellow LED DL5 keeps on flashing fast. The DIP n° 1
becomes uninfluential.
3. START
→
The motor stops in opening and the yellow LED DL5 switches on fixed. The control unit waits
for commands.
If in this phase the DIP n°1 is put on OFF, you leave the procedure, only saving the work time and disabling the
automatic closing. The yellow LED DL5 switches off and the next START command will cause the closing.
4. START
→
The pause time counting starts. The yellow LED DL5 flashes slowly.
In this phase, if the DIP n°1 is put on OFF, you leave the procedure, only saving the work time and disabling the
automatic closing. The yellow LED DL5 switches off and the next START command will cause the closing.
5. START
→
It ends the pause time counting, the work time and the pause time are memorized. The yellow
LED DL5 remains on fixed.
6. To leave the times learning procedure, put the DIP n° 1 on OFF and the next START command or
GENERAL_CLOSE will cause the closing.
To modify the memorized times, it is necessary to repeat the above procedure.
WARNING
During the times learning phase, the PHOTO, SAF, GENERAL_OPEN, GENERAL_CLOSE are disabled.
If the radio command is used as START, pay attention to the correct configuration of the dip n. 5 – 6 – 7 – 8.
DEFAULT VALUES
Work time: 30 s
Automatic closing disabled.