Safety operation of flammable refrigerant

Filling the refrigerant

1. Use the refrigerant filling appliances specialized for R32. Make sure that different kinds

of refrigerant won’t contaminate with each other.

2. The refrigerant tank should be kept upright at the time of filling refrigerant.
3. Stick the label on the system after filling is finished (or haven’t finished).
4. Don’t overfilling.
5. After filling is finished, please do the leakage detection before test running; another time

of leak detection should be done when it’s removed.

Safety instructions for transportation and storage

1. Please use the flammable gas detector to check before unload and open the container.
2. No fire source and smoking.
3. According to the local rules and laws.

Welding

If you should cut or weld the refrigerant system pipes in the process of maintaining, please 

follow the steps as below:

1. Shut down the unit and cut power supply.

2. Eliminate the refrigerant.
3. Vacuuming.
4. Clean it with N2 gas.

5. Cutting or welding.

6. Carry back to the service spot for welding.

The refrigerant should be recycled into the specialized storage tank.

Make sure that there isn’t any naked flame near the outlet of the vacuum pumpand it’s

well-ventilated.

45

Summary of Contents for MAMBA GIA-S09MAMB-I

Page 1: ...ment lisez attentivement les instructions Por favor leia atentamente este manual antes de usar o equipamento Per favore leggere attentamente questo manuale prima di utilizzare questo prodotto Gracias Thank you Merci Obrigado Grazie ES EN FR PT IT OWNER S AND INSTALLATION MANUAL MAMBA GIA S09MAMB I GIA S12MAMB I GIA S18MAMB I GIA S24MAMB I INDOOR UNIT ...

Page 2: ...OWNER S AND INSTALLATION MANUAL ENGLISH INDOOR UNIT MAMBA GIA S09MAMB I GIA S12MAMB I GIA S18MAMB I GIA S24MAMB I ...

Page 3: ...EU To prevent possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the return and collection systems or contact the retailer where the product was purchased They can take this product for environmental safe recycling If it needs to install move or maintai...

Page 4: ...rigerant with no harm to the ozonosphere The influence upon the greenhouse effect is also lower R32 has got very good thermodynamic features which lead to a really high energy efficiency The units therefore need a less filling The Refrigerant WARNING Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacture Should repair be necessary contact ...

Page 5: ...ly cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Do not wash the air conditioner with water to avoid electric shock Do not spray water on indoor unit It may cause electric shock or malfunction After removing the filter do not touch fins to avoid injury Do not use fire or hair dryer to dry the filter to avoid defo...

Page 6: ... block air outlet or air inlet It may cause malfunction Do not spill water on the remote controller otherwise the remote controller may be broken When below phenomenon occurs please turn off air conditioner and disconnect power immediately and then contact the dealer or qualified professionals for service Power cord is overheating or damaged There s abnormal sound during operation Circuit break tr...

Page 7: ...the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube The appliance shall be installed in accordance with national wiring regulations Installation must be performed in accordance with the require...

Page 8: ...ed by a professional If the length of power connection wire is insufficient please contact the supplier for a new one Avoid extending the wire by yourself For the air conditioner with plug the plug should be reachable after finishing installation For the air conditioner without plug an circuit break must be installed in the line If you need to relocate the air conditioner to another place only the...

Page 9: ...ir inlet Filter Air outlet Indoor unit Remote controller Actual product may be different from above graphics please refer to actual products NOTE Display Temp indicator Temp indicator Wi Fi indicator Wi Fi indicator For some model For some model 38 ...

Page 10: ...sconnect the power before cleaning the air conditioner to avoid electric shock Do not wash the air conditioner with water to avoid electric shock Do not use volatile liquid to clean the air conditioner Clean surface of indoor unit When the surface of indoor unit is dirty it is recommended to use a soft dry cloth or wet cloth to wipe it Note Do not remove the panel when cleaning it Clean filter Ope...

Page 11: ...k whether drainage pipe is damaged Checking after use season 1 Disconnect power supply 2 Clean filter and indoor unit s panel Notice for recovery 1 Most of packing materials are recyclable materials Please dispose them in appropriate recycling unit 2 If you want to dispose the air conditioner please contact local dealer or consultant service center for the correct disposal method Clean and mainten...

Page 12: ...display when operating remote controller Check whether remote controller appears to be damaged If yes replace it Fluorescent lamp in room Take the remote controller close to indoor unit Turn off the fluoresent lamp and then try it again No air emitted from indoor unit Air inlet or air outlet of indoor unit is blocked Eliminate obstacles Under heating mode indoor temperature is reached to set tempe...

Page 13: ... source Air conditioner operates normally suddenly Whether there s interference such as thunder wireless devices etc Disconnect power put back power and then turn on the unit again Water flowing noise Air conditioner is turned on or turned off just now The noise is the sound of refrigerant flowing inside the unit which is a normal phenomenon Cracking noise Air conditioner is turned on or turned of...

Page 14: ...ofessional person L1 PG motor indoor zero crossing detecting circuit malfunction Turn off restart after a few seconds if the code occurs again after a few minutes please contact the professional person L2 No feedback signal of indoor unit fan Turn off restart after a few seconds if the code occurs again after a few minutes please contact the professional person L3 L6 Communication malfunction Powe...

Page 15: ...a is shown on the nameplate or following table 1 4 Leak test is a must after installation Minimum room area m2 Charge amount kg 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 2 5 floor location 14 5 16 8 19 3 22 0 24 8 27 8 31 0 34 4 37 8 41 5 45 4 49 4 53 6 window mounted 5 2 6 1 7 0 7 9 8 9 10 0 11 2 12 4 13 6 15 16 3 17 8 19 3 wall mounted 1 6 1 9 2 1 2 4 2 8 3 1 3 4 3 8 4 2 4 6 5 5 5 6 0 ...

Page 16: ...d be done when it s removed Safety instructions for transportation and storage 1 Please use the flammable gas detector to check before unload and open the container 2 No fire source and smoking 3 According to the local rules and laws Welding If you should cut or weld the refrigerant system pipes in the process of maintaining please follow the steps as below 1 Shut down the unit and cut power suppl...

Page 17: ...ere should be noobstruction near air inlet and air outlet 2 Choose a place where the condensation water can be dispersed easily and won t affect other people 3 Choose a place which is convenient to connect the outdoor unit and near the power socket 4 Choose a place which is out of the reach of children 5 The place should be ableto withstand the weight of indoor unit and won t increase noise and vi...

Page 18: ...Be sure to cut off the power supply before proceeding any work related to electricity and safety 6 Do not connect the power before finishing inatallation 7 If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 8 The temperature of refrigerant circuit will be high please keep the interconnection cable away f...

Page 19: ...e pressure rise or compressor rupture resulting in injury 4 During refrigerant recovery make sure that liquid valve and gas valve are fully closed and power is disconnected before detaching the connection pipe If compressor starts running when stop valve is open and connection pipe is not yet connected air will be sucked in and cause pressure rise or compressor rupture resulting in injury To ensur...

Page 20: ...as around the unit it may cause explosion and other accidents 7 Do not use extension cords for electrical connections If the electric wire is not long enough please contact a local service center authorized and ask for a proper electric wire Poor connections may lead to electric shock or fire 8 Use the specified types of wires for electrical connections between the indoor and outdoor units Firmly ...

Page 21: ...position of piping hole should be a little lower than the wall mounted frame shown as below Left Wall Φ55 Φ70 Right Mark in the middle of it Level meter Rear piping hole Wall Space to the wall above 150mm Space to the wall above 150mm Φ55 Φ70 Rear piping hole Dimension 1081x327x248 Left Wall Φ55 Right Mark in the middle of it Level meter Rear piping hole Wall Space to the wall above 150mm Space to...

Page 22: ... the pipe from left or right please cut off the corresponding hole on the bottom case Step 5 Connect the pipe of indoor unit 1 Aim the pipe joint at the corresponding bellmouth 2 Pretightening the union nut with hand 3 Adjust the torque force by referring to the following sheet Place the open end wrench on the pipe joint and place the torque wrench on the union nut Tighten the union nut with torqu...

Page 23: ... connection wire to the wiring terminal according to the color tighten the screw and then fix the power connection wirewith wire clip 4 Put wiring cover back and then tighten the screw 5 Close the panel Note All wires of indoor unit and outdoor unit should be connected by a professional If the length of power connection wire is insufficient please contact the supplier for a new one Avoid extending...

Page 24: ...ass through the wall hole 2 Hang the indoor unit on the wall mounting frame 3 Stuff the gap between pipes and wall hole with sealing gum 4 Fix the wall pipe 5 Check if the indoor unit is installed firmly and closed to the wall Do not bend the drain hose too excessively in order to prevent blocking indoor unit gas pipe indoor and outdoor power cord liquid pipe drain hose band drain hose band connec...

Page 25: ...ter outlet can t be placed in water in order to drain smoothly Slant the drain hose slightly downwards The drain hose can t be curved raised and fiuctuant etc The drain hose can t raise upwards The water outlet can t be placedin water The drain hose can t be fluctuan The drain hose can t be fluctuant The water outlet can t be fluctuant 54 ...

Page 26: ...pply according to the voltage marked on the nameplate It may cause malfunction or damaging the parts Is electric wiring and pipeline installed correctly It may cause malfunction or damaging the parts Is the unit grounded securely It may cause electric leakage Does the power cord follow the specification It may cause malfunction or damaging the parts Is there any obstruction in the air inlet and ou...

Page 27: ...ting when first power on and turn on units to ensure the correct installation The steps of test operation is as below A Use remote controller to select cooling mode and set the temperature in 16 C Aim to the indoor display board press in 5s then the indoor display LL with a long whistle This indicates the units start to test operating B The test operating is finished when indoor display change to ...

Page 28: ...onnement et la santé dérivant d une élimination incorrecte et permet de récupérer les matériaux qui le composent dans le but d une économie importante en termes d énergie et de ressources Pour rappeler l obligation d éliminer séparément les appareils électroménagers le produit porte le symbole d un caisson à ordures barré ADVERTÊNCIA PARA A ELIMINAÇÃO CORRECTA DO PRODUCTO SEGUNDO ESTABELECIDO PELA...

Reviews: