10. WORK INSTRUCTIONS

      When the inverter is in work condition, the input voltage and output power will be 

shown  on  the  digital  display  screen  by  turns.  Likewise,  when  the  inverter  goes  into 

protection, corresponding letters will be also shown on the screen. Different letters 

mean the inverter is in different protection conditions.

1. When the input (V) LED is on, the current input voltage is shown.

2. When the output (KW) LED is on, the current output power (KW) is shown.

3. When the output (W) LED is on, the current output power (W) is shown.

4. LO means the inverter is in under voltage protection.

5. HI means the inverter is in over voltage protection.

6. OL means the inverter is in overload protection or short-circuits protection.

7. OH means the inverter is in OVER HEAT protection.

8. ABOUT SOFT START TECHNOLOGY

The output voltage rises up from low to normal when the inverter is turned on. This can 

reduce attack of high startup currents, which can make startup easier of large inductive 

loads.   

As  for  the  large  inductive  loads,  such  as  electric  tools  and  the  capacitive  loads, 

suggest  turning  on  the  switch  of  the  appliance  firstly  and  later  the  inverter's.  The  soft 

start works.

9. THE OUTPUT WAVE FORM

     The  output  wave  form  of  this  inverter  is  Pure  Sine  Wave,  which  is  much  like  the  one 

from  utility-supplied  AC  electricity,  even  more  purer;  pure  sine  wave  is  applicable  in 

most of loads, including electrical equipments, such as Linear Adaptor, switching power 

supply, transformer, and motor and so on. 

Comparing with Modified wave form, for inductive loads such as refrigerator and electric 

fans, pure sine wave form can improve its power factor and the battery's efficiency and 

reduce working noises effectively from appliances. For capacitive loads such as adapter 

of lap-top, pure sine wave can lower the rush current at work and reduce interferences to 

increase reliability and prolong the life of the product.  

Pure sine wave output

(240 VAC Model)

339 Volta peak

11. PROTECTION FUNCTION

1. Input under-voltage alarm:

 When the input DC voltage is lower than 9.8V 

/19.6V/39.2V, the buzzer will whistle intermittently to remind that the inverter will go 

into the under voltage protection. Pay attention to save the data if you are using 

computer.

2. Under voltage protection:

 The inverter will automatically shut down when the 

input DC voltage is lower than 9.5V/19V/38V. The buzzer will whistle continuously 

and the digital display screen will show LO. Please turn off the inverter and use it 

after recharging the battery.

3. Over voltage protection:

 The inverter will automatically shut down when the input 

DC voltage is higher than 16V/32V/62V. The buzzer will whistle continuously and 

the digital display screen will show HI. Please turn off the inverter and adjust the 

input voltage to the admissible range.

4. Overload protection:

 The inverter will automatically shut down when the load 

power is higher than the rated power. The buzzer will whistle continuously and the 

digital display screen will show OL. Turn off the inverter and resume to normal 

operation after taking away the redundant load.

5. Short-circuit protection:

 The AC output will be automatically shut down when 

short circuit. And the digital display screen shows OL. 

6. Thermal protection: 

The unit will be calorific during operation. If the temperature is 

higher than 65

, the inverter will automatically shut down. Then the buzzer will 

whistle continuously and the digital display screen shows OH. Please turn off the 

inverter, and continue using it after the temperature goes back to normal 

temperature naturally. Meanwhile find out the factors causing the fault, such as 

ventilation, ambient temperature, vent, load power and so on. It can avoid the 

similar things happen again.

12. QUICK KNOWLEDGE ABOUT INVERTER  

    

 ! Ensure Your Battery Size Is Big Enough And Voltage Is Correct.

A. CORRECTLY CONNECTING THE INVERTER FOR FIRST USE.

1) Secure the provided Negative (black) DC cable connect to the Negative (-) bolt on 

the inverter, and the other end to the Negative (-) post on the battery.

2) Secure the provided Positive (Red) DC cable to the Positive (+) bolt on the inverter, 

and the other end to the Positive (+) post on the battery.

3) The nuts of the connection posts must be tightened to ensure well connected.

4) Press the power switch for one second, because it is a long press type switch.

WARNING: REVERSE CONNECTED THE CABLES WILL DAMAGE THE 

INVERTER AND AVOID YOUR WARRANTY! 