Giacomini K492DY012 Manual Download Page 2

2

0954EN  June 2018

R

oom

 

contRol

 

and

 

electRonic

 

Regulation

W

eekly

 

chRonotheRmohumidistat

foR

 

exteRnal

 

Wall

-

mount

 

installation

k492dy012

Installation

Warning.

 This product must be installed by qualified operators only in 

compliance with standards provided for electric devices.

 The product must be installed with power off.

Chronothermohumidistat K492DY012 must be installed on a wall or inside a 
3-module or round wall-mount box at approximately 1,5 m from the floor and 
in a position suitable to read the room temperature.
Do not install the thermostat on outside walls, near doors and windows and 
in positions under direct sunlight.

Follow the steps below to install the chronothermohumidistat:

 Separate the back cover from the body prying on the slot.

 Remove the insulation by unscrewing the special waterproof screw.

 Connect the wires (see “Electric connections”) and fit the back cover on the 

wall using the screws included.

 Tighten the screw and snap the body on the back cover.

Electric connections

Connect the electric wires using the diagram below as reference.

5

B

6

A

7

1

K492DY012

2

Gd

4

L

N

In2

In1 Gd

Relè 2

(dehumidificator)

Relè 1

(heating/

cooling)

Optional probe

K463PY001

Input 1

(allarme)

230V 50Hz

Input 2

(changeover)

Warning.

 Connect the electric wires with power off.

 The electric wires must be connected by qualified operators only.

Note.

In case of blackouts, the settings will not be deleted as they are saved 
in a non-volatile memory. Uninterrupted operation of the clock/
calendar in case of extended network failure is also guaranteed by an 
internal back-up battery.

Reviews: