Limit switch GS125
Assembly and installation
Mechanical assembly
The installation of multiple devices without spacing is only permitted with a horizontally mounted DIN rail.
Electrical Installation
The device may only be installed by a qualified electrician. The national and international regulations for the
installation of electrical systems of the respective operator country apply.
Power supply according to DIN EN 60664-1. SELV, PELV
For the installation of the inputs and outputs, refer to the connection diagram.
The auxiliary voltage is connected to connections 11 and 12 of the pluggable terminal block.
Terminals 41, 42, 51, 52 are used for sensor connection
Terminals 21, 22, 31, 32 are used for relay output. Circuit depends on device type.
Terminals 61, 62 are used for the analogue output
Elektrische Anschlüsse
Terminals
Assignment
11
Power supply ~/+
12
Power supply ~/-
Switching outputs*
GS125x-1
GS12x-2
GS125x-3
21
Relay contact
A1
A1, A2
COM A2
22
Relay contact
-
A2
A2
31
Relay contact
COM A1, A2
COM A1, A2
COM A1
32
Relay contact
A1
A1
A1
Signal inputs
PT100 / Poti
Thermocouple J /K /S
Current
Voltage
41
Red** /S
+ black/green/orange***
+
42
Red** /
+
51
White** /A
52
/E
- white / white / white**
-
-
61
Analogue output
+ 4…20 mA
62
Analogue output
– 4…20 mA
Table 3 Electrical connections
*
Take care of actual limit function (Min/Max)! Please also see
** Description acc. to IEC 60751, different colour coding possible
*** Description acc. to IEC 584, different colour coding possible
Danger
Figure 6 rail mounting TS35, DIN EN 60715
Summary of Contents for Martens GS125L
Page 1: ...Operating Manual Limit switch GS125L EN Save for later reference ...
Page 24: ...BA_MA_GS125_EN_V1 04 22 24 Limit switch GS125 Certificate of Conformity ...
Page 25: ...BA_MA_GS125_EN_V1 04 23 24 Limit switch GS125 Notes ...
Page 26: ...BA_MA_GS125_EN_V1 04 24 24 Limit switch GS125 Notes ...