BAROsense
- 16 -
V1.2
Address
Description
Format
6
Enable/disable the offset of the voltage analog output:
0=offset disabled (default, 0…1/0…5/0…10 V)
1=offset enabled (0,2…1/1…5/2…10 V)
Bit
7
Sets the direct or reversed correspondence between voltage
analog output and pressure:
0=direct (default, Min. V
Min. press., Max. V
Max.
press.)
1=reversed (Min. V
Max. press., Max. V
Min. press.)
Bit
Holding Registers:
Address
Description
Format
0
RS485 Baud Rate:
0=1200;
1=2400;
2=4800;
3=9600;
4=19200 (default);
5=38400;
6=57600;
7=115200.
16-bit Integer
1
RS485 parity and stop bits:
0=8N1;
1=8N2;
2=8E1 (default);
3=8E2;
4=8O1;
5=8O2.
[N=no parity, E=even parity, O=odd parity]
16-bit Integer
2
Instrument address for the MODBUS-RTU protocol (1…247,
default=1).
16-bit Integer
3
Pressure unit of measurement:
0
Torr,
1
Pa,
2
hPa,
3
kPa,
4
mbar,
5
psi,
6
kg/cm
2
,
7
mmH
2
O,
8
mmHg,
9
mmH
2
O,
10
inHg,
11
atm,
12
bar
Default
: 2
hPa
16-bit Integer
4
Offset added to the measured pressure value.
For the value, see
Note 3
below.
The offset must be within the ±10 hPa range or equivalent
range in the set unit of measurement, if different from hPa.
Default
: 0.
16-bit Integer
5
Temperature unit of measurement:
0
°C,
1
°F
Default
: 0
°C
16-bit Integer
6
Measurement interval in seconds (1…30, default=1).
16-bit Integer
8
Minimum pressure value for the current analog output.
For the value, see
Note 3
below.
Default
: 60000 (=600.00 hPa)
32-bit Integer
(2)