GHM Messtechnik GmbH – Martens
Kiebitzhörn 18
● 22885 Barsbüttel ● Germany
Phone +49-40-670 73-0
● Fax
-288
www.ghm-messtechnik.de
●
5
1.4.
Standards and directives
Low-voltage Directive 2014/35/EU
Testing standard 60664-1: 2007
EMC Directive 2014/30/EU
Testing standard EN 61326-1: 2013
RoHS Directive 2011/65/EU
Testing standard EN50581: 2012
ATEX Directive 2014/34/EU
Testing standards EN60079-0: 2012, EN60079-11:2012, EN60079-15: 2010
Functional safety
Testing standards EN61508-1: 2010
(Issue years for testing standards belong to german versions)
2.
Product description
Switch amplifiers of the series TS125 and TS255 are used in switch cabinets for
the conversion and isolation of digital switching signals, optionally also in explosive
areas.
The devices are available in one- or two-channel versions.
All passive sensors, such as switching contacts, Namur initiators according to DIN
EN 60947-5-6, or passive electronic outputs of third-party devices, can be
connected to the optional intrinsically safe inputs.
The TS125 series in 12.5mm wide carrier rail housing offers relay outputs with
output make circuit.
The TS225 series in 22.5mm wide carrier rail housing offers relay outputs with
changeover function.
The devices may also be used in explosion zone 2 if they are installed in a suitable
housing.
Use in plants with functional safety SIL2 is also possible.
Input 1
Input 2
Relay A1
Relay A2
Power supply