16
4
Mounting
Electrical installation
Modbus
4.3.3
CANopen
Typical topologies
Terminal description
CANopen
Connection
X216
Connection type
Spring terminal
Min. cable cross-section
AWG
22
Max. cable cross-section
AWG
12
Stripping length
inch
0.39
Tightening torque
lb-in
-
Required tool
0.4 x 2.5
Basic network settings
Use the DIP switch to set the node address and baud rate and to activate the integrated bus terminating
resistor.
Bus termination
Baud rate
CAN node address
R
d
c
b
a
64
32
16
8
4
2
1
OFF
OFF
ON
OFF
ON 20 kbps
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Inactive
OFF OFF
ON
ON 50 kbps
Value from parameter
ON
OFF OFF
ON
OFF 125 kbps
Node address - example:
Active
OFF OFF OFF
ON 250 kbps
OFF OFF ON OFF ON ON ON
OFF
OFF
OFF
OFF
Value from parameter
(
500 kbps
)
Node address = 16 + 4 + 2 + 1 = 23
OFF
ON
OFF OFF 1 Mbps
All other combinations
Value from parameter
(
500 kbps
)
Printed in bold
= Emotron setting
The network must be terminat
ed with a 120 Ω
resistor at the physically first and last node.
Set the "R" switch to ON at these nodes.
CH
CL CG
CH
CL
CH
CH
CL
CG
Line
A1
A2
A3
An
120
120
120
120
R
R
X216
X216
CG
R
X216
CL CG
R
X216
a
O
N
R
d c
b
1
2
4
8
16
32
64
CAN Address
Baud
Summary of Contents for DSV3540013
Page 1: ...Emotron DSV35 AC drive 4 10 hp Use in UL approved systems Mounting and switch on instruction...
Page 2: ...This page intentionally left blank...
Page 10: ...10 4 Mounting Mechanical installation Dimensions 10 hp All Dimensions in inch...
Page 11: ...11 Mounting Mechanical installation 4 This page is intentionally left blank...
Page 27: ...Technical data 6 27...