Using the monitoring, the instruction manual of the electric actuator type 
EA 25-250 must be observed. 

 

Intended use 

Accessory board Fail-safe return unit 

The monitoring can be used with the electric actuators type EA25, EA45, 
EA120 and EA250, both with the 24V AC/DC as well as the 100-230V AC 
version. The board is to be plugged into the housing of the actuator in the 
provided slots. The fail-safe return unit already includes the required 
battery; no external wiring is necessary. The board is also available 
without a battery for connecting an emergency external power source 
with 24 V DC. 

 

Description

Description

Description

Description    

Technical data

Technical data

Technical data

Technical data    

Code

Code

Code

Code    

Fail-safe return unit 

With integrated battery pack 

199 190 610 

Fail-safe return unit 
external 

Voltage supply implemented 
externally (24 V DC) 

199 190 611 

 

    
    
    
    
    
    
    
    

 

1

 

Function 

In case of a failure of the supply voltage, the battery is electronically 
switched on automatically after 5 s. With the selector switch on the board, 
the functions "Move to CLOSE position" or "Move to OPEN position" can 
be selected. 
 
Fail-safe return unit with battery            Fail-safe return unit external 
 
 
 
 
 
 
 
 
 
 
 
 

Switch position 

Switch position 

Switch position 

Switch position Failsafe 

Failsafe 

Failsafe 

Failsafe 

return unit

return unit

return unit

return unit    

Function

Function

Function

Function    

Switch left 

Actuator moves to OPEN (counterclockwise) 

Switch right (standard) 

Actuator moves to CLOSE (clockwise) 

The batteries are always stored charged. If the battery charges level 
drops below 50 %, the actuator LED flashes yellow and the charge cycle 
starts. Once U

Batt

 rises above 50 %, the flashing stops. 

During the charge cycle, the actuator can be operated normally. When 
charging the internal Error LED displays “L”. The ready to operate signal 
stays. 
 

Switch posit

Switch posit

Switch posit

Switch position fail

ion fail

ion fail

ion fail----safe 

safe 

safe 

safe 

rerturn unit external

rerturn unit external

rerturn unit external

rerturn unit external    

Function

Function

Function

Function    

Switch above 

Actuator moves to OPEN (counterclockwise) 

Switch below 

Actuator moves to CLOSE (clockwise) 

 

2

 

Assembly of the fail-safe return unit board 

The push button on the right side of the PCB is used to check the charge 
status of the batteries. If status is “ok” the LED on the PCB will light up 
green after pressing this button. If no green light occurs do not use this 
PCB. 

 

    

The board must not be plugged into the actuator while the green LED is 

The board must not be plugged into the actuator while the green LED is 

The board must not be plugged into the actuator while the green LED is 

The board must not be plugged into the actuator while the green LED is 
activated

activated

activated

activated    on the.

on the.

on the.

on the.PCB.

PCB.

PCB.

PCB. 

LED turns off after 30s, then the board is ready to be installed. 

 

 

    

Disconnect the actuator from the supply voltage.

Disconnect the actuator from the supply voltage.

Disconnect the actuator from the supply voltage.

Disconnect the actuator from the supply voltage. 

 

 

1.

 

Remove housing cover of the electric actuator (loosen the 4 screws, 
open cover). 

2.

 

Take the fail-safe return unit board out of the packaging and check for 
damages. 

 

 

    

Do not touch the board itself. Electrostatic discharge can damage the 

Do not touch the board itself. Electrostatic discharge can damage the 

Do not touch the board itself. Electrostatic discharge can damage the 

Do not touch the board itself. Electrostatic discharge can damage the 
components.

components.

components.

components. 

 

3.

 

Insert board vertical on the backside of the main board onto the red 
plug. 

 

 

    

Ensure that the board sits in the lateral 

Ensure that the board sits in the lateral 

Ensure that the board sits in the lateral 

Ensure that the board sits in the lateral guides and snaps.

guides and snaps.

guides and snaps.

guides and snaps. 

 

3

 

Test functioning of the fail-safe return unit 

Apply power to the actuator and move into position OPEN. Remove power 
to the actuator. Actuator moves after about 5s to CLOSE position (or 
reversed, depending on the setting of the switch). 

 

4.

 

Put the cover back in place and fasten it with the 4 screws. 

 

4

 

Error message 

An error can triggers the following: 

 

The 7-segment display on the main board illuminates; see illustration 
below.  

 

The ready-to-operate signal will be off (terminals 5,6 NO contact) 

 

LED flashes yellow (except in case of power outage) 

 

 

 

Assignment of error codes for error messages 

If the fail-safe return unit PCB is installed, the following error codes can 
be displayed: 

 

Error code

Error code

Error code

Error code    

Description

Description

Description

Description    

Signal „Ready

Signal „Ready

Signal „Ready

Signal „Ready----
to

to

to

to----operate“

operate“

operate“

operate“    

EA re

EA re

EA re

EA response

sponse

sponse

sponse    

Battery voltage < 50%  Yes 

Normal operation 

Battery faulty 

No 

Normal operation 

 

For further error codes of the main board, see instruction manual of the electric 
actuator type EA 25-250. 
 

Acknowledge error message

Acknowledge error message

Acknowledge error message

Acknowledge error message    
Check the cause of fault, if necessary, carry out relevant maintenance. 

 

 

    

The message can be eliminated while the supply voltage is still connected 

The message can be eliminated while the supply voltage is still connected 

The message can be eliminated while the supply voltage is still connected 

The message can be eliminated while the supply voltage is still connected 
or the actuator is briefly disconnected from the mains voltage (does not 

or the actuator is briefly disconnected from the mains voltage (does not 

or the actuator is briefly disconnected from the mains voltage (does not 

or the actuator is briefly disconnected from the mains voltage (does not 
work with cycle monitoring).

work with cycle monitoring).

work with cycle monitoring).

work with cycle monitoring).    

 

Error can be acknowledged via the „SET“button on the main board. 

+24V DC | 0V 