25
2.3
PILOT SPRING OPTIONS
The desired setpoint pressure
MUST
lie within the pilot spring pressure range. The pilot spring can
be identified from the ‘Spring Colour Indication Washer’.
It is recommended that the pilot spring is selected so that the maximum setpoint pressure is near to
the upper limit of its pressure range, e.g. for 7 bar setpoint pressure, a black spring is
recommended.
Spring
Colour
Max.
Downstream
Pressure (Bar[g])
Adjustment
sensitivity
(Bar/full turn)
Black*
8.5
0.43
Blue
17
0.65
Red
25
1.5
*Standard
**With locknut removed