UFO-NT
24
Configurable inputs
11.5 Emergency lock
WARNING
Danger of injury due to crushing and shearing!
The safety sensors and the obstacle are not evaluated. The door closes with the set force.
X
If the door closes suddenly, move out of the hazard zone.
Not permissible in the case of rebated doors and escape routes.
Only a configurable input may be used.
à
The configurable inputs PE2 and PE3 can be used to connect an emergency lock switch.
à
When the emergency lock switch is activated, the contact is closed and 17.83 V is applied to the input PE2 or
PE3. Contact sensors KA, KI, and KB, sensor strips SIS and SIO and obstacle detection are hidden. Hold open
operating mode is cancelled. The door closes and locks. The function requires a terminating resistor of 20
kOhm for proper use.
à
The door remains closed as long as the emergency lock signal is applied to the input.
à
Set the parameters with:
à
DPS:
Set
e2
or
e3
to
07
(emergency lock.20 KOhm).
à
ST220: Set "PE2 function" or "PE3 function" to "Emergency lock.20KOhm NO".
PE2
24V
PE3
24V
52
2
PE2
PE3
oder
53
2
20 k
Ω
11.6 Additional contact sensors (P-KI, P-KA)
à
The configurable inputs can be used to connect additional normally open contacts as contact sensor inside or
outside.
à
Set the parameters with:
à
DPS: Set
e1
,
e2
or
e3
to
0 8
(contact sensor inside) or to
0 9
contact sensor outside).
à
ST220: Set "PE1 function", "PE2 function" or "PE3 function" to "P-KI actuation NO" or "P-KA actuation NO".
à
For more information see chapter 7 "Contact sensor inside" or chapter 8 "Contact sensor outside".
à
The contact sensors can either be connected to terminal 2 (24 V) or terminal 4 (24 VSens).
11.7 Switch function
11.7.1 General information
à
Upon activation, the output of the push button is closed (24 V applied to the PE1 or PE2 input).
à
In the case of 2-leaf systems, the push button can be connected to the active leaf controller or to the passive
leaf controller.
X
Set the hold-open time at the active leaf control.
à
If the push button is connected to the passive leaf control, both door leaves open when the switch function
is activated, even if the "1-leaf" mode of operation is set. The operating mode “Automatic” must be set on the
passive leaf.
11.7.2 Switch function
DPS
X
Set
e1
or
e2
to
1 0
for:
1 switch contact = open door / 2nd switch contact = close door.
If no second switch contact takes place, the door remains open until the mode of operation is changed.
For a 2-leaf drive, opening is double leaf if the button is connected to the passive leaf drive.
ST220
X
Set "PE1", "PE1 function" or "PE2", "PE2 function" to "Push button NO” for:
1 switch contact = open door / 2nd switch contact = close door.
If no second switch contact takes place, the door remains open until the mode of operation is changed.