TSA 160 NT
30
Mode of operation
13 Mode of operation
à
To operate the display programme switch DPS see chapter 24.1, “Display programme switch (DPS)”.
à
To operate the service terminal ST220 see chapter 23.2, “Operation of ST220”.
13.1 Internal programme switch
à
Internal programme switch, 300 mm, mat. no. 105186
à
Internal programme switch, 640 mm, mat. no. 105187
Active leaf control
à
The internal programme switch has the switch positions:
à
NA (0)
à
AU (II)
à
DO (I).
à
The mode is set with the AU and DO inputs. The drive switches
to AU or DO mode if 24 V is applied to the corresponding
input. In NA mode there is no signal at these inputs.
GF ES
1
WAB
2
OL
3
DO
4
24V
5
24V
6
24V
7
AU
I
0
II
BU
RD
YE
X
Set the parameters (internal or external binary programme switch):
à
DPS: Set
ps
automatic contact type to value
01
for “normally opened contact”.
à
ST220: Set “Signals”, “Input signals”, “AU” to value “normally opened contact”.
Set “Signals”, “Input signals”, “DO” to value “normally opened contact”.
à
S1, S2: Set parameter 19 to value 01 for “normally opened contact”.
à
The change of the operating mode with TPS or DPS is only possible if the internal programme switch has been
set to the position NA (0).
Passive leaf control
à
The inputs AU (II) and DO (I) are used to switch the
drive of the passive leaf on and off. The passive leaf
runs synchronously with the active leaf (in compli-
ance with the closing sequence), if 24 V is applied
at one of the two inputs.
SF ES
1
WAB
2
OL
3
EIN
4
24V
5
24V
6
24V
7
EIN
I
0
II
BU
RD
YE
13.2 Mechanical programme switch (MPS, external programme switch)
à
MPS, AS500, mat. no.113226
à
MPS-ST, with key, AS500, mat. no. 113227
à
Operating modes:
OFF, NA, LS, AU 1-leaf, DO, AU 2-leaf
X
Follow the installation instructions.
à
At 2-leaf systems connect to the active leaf.
à
The malfunction indication (LED) is not operable.
à
Accessories:
à
Surface-mounted cap, single, AS500, mat. no.
120503
X
Set the parameters (for MPS):
à
DPS: Set
ps
, automatic contact type to value
0 3
for “Analogue MPS”.
à
ST220: Set “Signals”, “Input signals”, “AU” to value “Analogue MPS”.
à
S1, S2: Set parameter 19 to value 03 for “Analogue MPS”.
X
Disconnect internal programme switch (disconnect red wire and insulate).