Technical data
State / fault
LED
Alarm output
Hold-open output
KL1: 3-4 / KL3: 1-2
Voltage-free
Off
10
11
12
AL_NC
AL_COM
AL_NO
0 V
Normal operation
Green
10
11
12
AL_NC
AL_COM
AL_NO
24 V
Contamination (warning)
The lintel-mounted smoke switch should be
replaced.
Red
Green
GN
RD
24 V
Contamination limit reached
The lintel-mounted smoke switch must be replaced.
Red
Green
GN
RD
0 V
Fault lintel-mounted smoke switch
The lintel-mounted smoke switch must be replaced.
Red
Off
aus
RD
0 V
Short-circuit at the hold-open output
Disconnect the lintel-mounted smoke switch from
the supply voltage and eliminate the short-circuit.
Red
Off
aus
RD
0 V
Supply voltage for lintel-mounted smoke
switch too small
Broken cable manual trigger switch
1)
Red
Off
aus
RD
0 V
Supply voltage ceiling-mounted detector too small
1)
Short-circuit ceiling-mounted detector
1)
Red
Off
aus
RD
0 V
Manual trigger switch activated
2)
Short-circuit manual trigger switch
1)
Yellow
0 V
Press the test button
Yellow
0 V
Alarm lintel-mounted smoke switch
Alarm ceiling-mounted detector
Broken cable ceiling-mounted detector
1)
Ceiling-mounted detector removed
Red
10
11
12
AL_NC
AL_COM
AL_NO
0 V
1)
Display only if line monitoring is active (jumper J3)
2)
Does not apply if the manual trigger switch is connected as a normally closed contact. When the
normally closed contact is actuated, “broken cable manual trigger switch” is displayed.
Tab. 4.4.1
4.5 Wireless module GC 171
Wireless module GC 171
ID 163051
Colour
RAL 7016 (anthracite grey)
Dimensions (W × H × D)
177 mm × 30 mm × 18 mm
Installation position
Wall installation
Input voltage
24 V DC
Input current
maximum 15 mA
Function
The wireless module GC 171 makes wireless communication possible
between the lintel-mounted smoke switch GC 151 and various wireless
devices (wireless smoke detector GC 172, wireless thermal detector GC
173 and wireless input module GC 175).
The wireless module GC 171 forwards wireless signals to the lintel-
mounted smoke switch GC 151 as changes in resistance. These changes
in resistance correspond to those of the ceiling-mounted detectors GC
152 and GC 153 and the manual trigger switch.
An alarm triggered at a wireless module is indicated without delay (in less
than 10 s) at the lintel-mounted smoke switch GC 151.
Interference with a wireless device or a problem with communication
is indicated in less than 100 s on the lintel-mounted smoke switch GC 151.
Number of wireless participants
The wireless module GC 171 can communicate with a maximum of 6
wireless devices (GC 172, GC 173 or GC 175).