background image

-1-

Instruction Manual

MCB / RCCB with Auto Reclosing

Panel Diagram

Wiring Diagram

General

Applications

     -Can be widely used in power grid terminal line, such as meter box, 
       new energy circuit management, PV solar control box, smart elec-
       tricity, smart home, new energy vehicle charging pile, and so on.

Function Features

     -It can be matched with circuit breaker / leakage protection switch 
      and automatically reclose when MCB / RCCB trips unexpectedly,
      No need for manual closing, reduce the cost of manual maintenance, 
      and eliminate faults in time to improve efficiency.
     -built in 3 reclosing times, continuous closing failure within 15 minutes
      can send alarm through auxiliary contact.
     -With manual / automatic selector switch.
     -With mechanical / electronic double locking function.
     -The shaft transmission mode is more stable and reliable.
     -Can match other accessories.
     - Work status is indicated by LED.
     - 1-MODULE. 

GRD9L

GRD9L Series

D48:DC24V-48V
A220:AC220V

D12:DC12V

Rated control supply voltage:

Model and connotation

Auto ReAUX

Technical parameters

Control mode

Supply terminals

A1-A2

Voltage range

DC12V,DC24V-48V

DC max.1W(standby)   max.20W(action)

Power input

Supply voltage tolerance

Supply indication

red LED

No trip or manual reset within 15 minutes after successful closing

Auto reclosing times

10000

Mechanical life

Electrical life(AC1)

-20

 to

 +

55

℃(-

4

℉ 

to

 

131

℉)

-35

 to

 +

75

℃(-

22

℉ 

to

 

158

℉)

Din rail EN/IEC 60715

IP20

any

solid wire max.1

×

2

.

5or 2

×

1

.

5

/

with

 

sleeve max.1

×

2

.

5

(

AWG

 

12

)

82

×

18

×

78mm

80g

Operating temperature

Storage temperature

Mounting/DIN rail

Protection degree

Operating position

Overvoltage cathegory

Pollution degree

Dimensions

Weight

GRD9L-R

Auto Reclosing

Voltage range

AC 220V(50-60Hz)

AC max.1VA(standby) max.20VA(action)

Power input

4000

Action time

≤1s

Auxillary contact

Alarm contact

Shunt release

Under voltage release

Yes

Yes

Yes

Yes

-10%;+10%

-10%;+10%

Supply voltage tolerance

AUTO

MANU

PWR

LOCK

GYL9

I

n

0.03A

230V~  t≤0.1s

T

e

s

t M

o

n

th

ly

Im=I

m=500A

Inc=I

c=6000A

40A

IEC 61008
EN 61008

N

1

T

N

2

Status indicator

Mode selection

Closing lock

Operation handle

RCCB/MCB

R

Note: The matching MCB / RCCB specification and model shall 
           be indicated when ordering.

     

  Example 1: GRD9L-R + GYM9 2P C40

           Example 2: GRD9L-R + GYL9 2P 40A 30M

1

2

3

4

A1

A2

AC220V

GRD9L-R

AUX

MAX100mA

COM NC

3

Auto reclosing interval time

10s-60s-300s

Reset the closing times

GEYA ELECTRICAL CO.,LTD

Add:Wenzhou Brige Industrial Zone,Beibaixiang Town,
Yueqing,Zhejiang,China 325603

Tel:0086-577-62771036
Fax:0086-577-62711079
E-mail:[email protected]
Web:www.geya.net

Combination with accessories

GRD9L

Summary of Contents for GRD9L-R

Page 1: ...y indication red LED No trip or manual reset within 15 minutes after successful closing Auto reclosing times 10000 Mechanical life Electrical life AC1 20 to 55 4 to 131 35 to 75 22 to 158 Din rail EN IEC 60715 IP20 any solid wire max 1 2 5or 2 1 5 with sleeve max 1 2 5 AWG 12 82 18 78mm 80g Operating temperature Storage temperature Mounting DIN rail Protection degree Operating position Overvoltage...

Page 2: ...ly to stabilize Then the green indicator light will stay on if When MCB RCCB fails to trip the red indicator light will be on Note that red during auto reclosing delayThe color will flash After the delay it will switch on automatically and the green light will be on Note When checking the circuit the RCCB MCB can not close when the lock function is activated Cooperate with RCCB Cooperate with MCB ...

Page 3: ...60s OFF 300s ON OFF LOCK 15min 15min AUX PWR AUTO MODE GRD9L D has automatic closing function The closing logic is shown in the figure below Alarm lamp AUTO MANU AUTO MANU PWR LOCK GYL9 I n0 03A 230V t 0 1s Test Monthly Im I m 500A Inc I c 6000A 40A IEC 61008 EN 61008 N 1 T N 2 LOAD L N C16 230V 3000 IEC 60898 1 1 2 ON OFF C25 400V 3000 IEC 60898 1 ON OFF 3 4 1 2 C16 230V 3000 IEC 60898 1 1 2 ON O...

Page 4: ...ot and whether it is slipped Common faults Dimensions mm 82 45 49 5 78 35 AUTO MANU PWR PWR PWR PWR PWR PWR PWR GRD9L GRD9L GRD9L GRD9L GRD9L GRD9L GRD9L LOCK GRD9L GYL9 2P GRD9L GYL9 4P AUTO MANU LOCK GYL9 I n0 03A 230V t 0 1s Test Monthly Im I m 500A Inc I c 6000A 40A IEC 61008 EN 61008 N 1 T N 2 GYL9 I n0 03A 230V t 0 1s Test Monthly Im I m 500A Inc I c 6000A 40A N 1 T N 2 3 4 5 6 IEC 61008 EN ...

Reviews: