FINE TUNING
22
Rotate the detector’s left potentiometer edge (Figure
G
) to set the minimum light level
under which the device will send the activation message on detecting movement. The
sensitivity increases by rotating the potentiometer counter clockwise and decreases by
rotating it clockwise.
The transmission period set through the Easy base unit can be regulated manually by
± 50% rotating the right local potentiometer on the detector (Figure
H
).
For instance, setting a time of 30 seconds on the Easy base unit, it will be possible
to continuously regulate the transmission period from 15 to 45 seconds.
Adjusting the intervention threshold
on the twilight sensor
potentiometer positioin
sensitivity
counter clockwise stroke end 10 lux (nearly dark)
centre position
80 lux
clockwise stroke end
exclusion of the twilight switch
(just before the exclusion it reaches 500 lux)
Potentiometer position
regulation of the set transmission period
Counter clockwise stroke end 50% (half the time set through the Easy base unit)
centre position
100% (time set through the Easy base unit)
clockwise stroke end
150% (1.5 times the time set through the Easy base unit)
Manual regulation of the transmission period