17
URS 60, URS 61 - Installation & Operating Manual -
819634-00
Technical data
Supply voltage
■
■
24V DC +/-20 %
Power consumption
■
■
max. 7 VA
Current input
■
■
max. 0.3 A
Internal fuse
■
■
T2A
Input/output
■
■
Interface for CAN bus to ISO 11898, CANopen, insulated
Safety circuit output
■
■
2 volt-free changeover contacts, connected externally in series. Contact material AgNi
■
■
Maximum switching current at switching voltages of 24 V AC/DC, 115 V AC and 230 V AC: resistive/
inductive 6 A
■
■
Connected contactors must have interference suppression (RC combination) as per the manufacturer's
specification
Required external fuse for safety circuit
■
■
T 2 A or T 1A (T = slow blow) for (TRD 604 *), 72 hrs of operation
* see page 9
Signal output
■
■
4 PhotoMOS outputs for external signalling, with or without delay
■
■
24 DC, max. current load 100 mA, NO characteristic
Test input
■
■
4 opto-coupler inputs for external test triggering, high active, 24 V DC +/- 20 %
Output relay switch-off delay
■
■
Factory default setting 3 seconds.
■
■
Option of 10 seconds and 15 seconds
Indicators and controls
■
■
4 x buttons for operation/for initiating test function in sensor
■
■
4 x green LEDs for indicating the active channels
■
■
4 x red LEDs for indicating a malfunction/alarm
■
■
3 x yellow LEDs for indicating internal errors and external sensor errors
■
■
1 x 10-pole code switch for setting the number of limiters, the delay and baud rate
Summary of Contents for URS 60
Page 1: ...Original Installation Operating Manual EN English Safety Control Unit URS 60 URS 61 819634 00 ...
Page 37: ...37 URS 60 URS 61 Installation Operating Manual 819634 00 For your notes ...
Page 38: ...38 URS 60 URS 61 Installation Operating Manual 819634 00 ...
Page 39: ...39 URS 60 URS 61 Installation Operating Manual 819634 00 ...