NRS 2-50, NRS 2-51 - Installation & Operating Manual - 

819179-05

In the control cabinet: Wiring the level switch

Wiring diagram for level switch NRS 2-51

5

  Supply voltage connection 

24 V DC

 with 0.5A semi-delay fuse provided on site

6

  Level electrode NRG 21-..; NRG 26-21 

 

Max. three NRS/NRR 2-5.. units can be connected. (connection in parallel).

7

  Level transmitter NRGT 26-., 4-20 mA, with shield connection in terminal box. 

 

Max. three NRS/NRR 2-5.. units can be connected (series connection).

8

  Central earthing point (CEP) in control cabinet

9

  MIN output contact, off delay 3 seconds

0

  MAX output contact, off delay 3 seconds

a

  Pump output contact

b

  Actual value output 4-20 mA 

Key

5

7

9

8

a

0

6

NRS 2-51

Fig. 4

0.5A  

(semi- 

delay)

 

b

MIN

MIN

MAX

MAX

b

5

9

a

0

0.5A  

(semi- 

delay)

 

8

continued

Summary of Contents for NRS 2-50

Page 1: ...E N English Original Installation Operating Manual 819179 05 Level Switch NRS 2 50 NRS 2 51 ...

Page 2: ...cturer s Declaration 5 Approval for marine use 5 Technical data NRS 2 50 NRS 2 51 6 Product package 7 Name plate identification 8 Installation Installation in the door of the control cabinet 9 Dimensions of the NRS 2 50 NRS 2 51 10 Key 10 Installation in a control cabinet 10 In the control cabinet Wiring the level switch Wiring diagram for level switch NRS 2 50 11 Key 11 Wiring diagram for level s...

Page 3: ...15 Operating the level switch Meaning of codes on the 7 segment display 17 Setting the measuring range 18 Bringing into service Setting parameters 19 Setting the measuring range 20 Operation alarm and testing Setting switchpoints and indicators 21 Indications 22 Checking the function of the MIN MAX output contacts 22 Passwort protection 23 Troubleshooting Indications diagnosis and remedies 24 Furt...

Page 4: ... an interval level control system fill discharge switch selectable With this equipment if the lower or upper water level switchpoint is reached the controller output contact switches depending on which function is set which then turns the feedwater pump on or off The amber LED lights up when the level switch has switched the feedwater pump on for example Faults or malfunctions in the level electro...

Page 5: ...rective and EMC Electromagnetic Compatibility The equipment conforms to the requirements of the Low Voltage Directive 2014 35 EU and the EMC Directive 2014 30 EU Notes on the Declaration of Conformity Manufacturer s Declaration For details on the conformity of our equipment with European Directives please refer to our Declaration of Conformity or our Manufacturer s Declaration The current Declarat...

Page 6: ... 51 1 analogue output 4 20 mA max output load 500 ohms e g for actual value indication Displays and controls 1 rotary knob with integrated pushbutton for testing the MIN MAX alarm and setting the parameters 1 four digit seven segment LED display green 2 red LEDs for MIN MAX alarm 1 amber LED e g for feedwater pump on NRS 2 51 1 four pole code switch for configuration Housing Housing material base ...

Page 7: ...24 hours Relative humidity Max 95 non condensing Approvals TÜV Certificate VdTÜV Bulletin Wasserstand 100 Water Level 100 Requirements for water level control and limiting equipment Type approval no TÜV WR XX 425 see name plate UL cUL CSA certification UL 508 and CSA C22 2 No 14 13 Standards for Industrial Control Equipment File E243189 Technical data Product package NRS 2 50 1 level switch NRS 2 ...

Page 8: ... P40 GESTRA AG Münchener Str 77 28215 Bremen Made in Germany Name plate identification Name plate bottom Type designation Fig 2 IP rating Safety note Output contacts Ambient temperature External fuse for output contacts Type approval number Disposal info Supply voltage Power consumption Fuse provided on site Technical data Serial number Actual value output Name plate of NRS 2 50 top Name plate of ...

Page 9: ...lled in the door of a control cabinet The advantage of using the adapter is that the status is visible and alarms can be tested without open ing the control cabinet door When installed the adapter has a rating of IP65 Please refer to the panel adapter Installation Operating Manual 850625 xx for further information Installation in the door of the control cabinet ...

Page 10: ...RS 2 50 NRS 2 51 1 Upper terminal strip 2 Lower terminal strip Key Installation in a control cabinet The NRS 2 50 NRS 2 51 level switch is clipped onto a type TH 35 EN 60715 support rail in the control cabinet Fig 1 4 3 Housing 4 Support rail TH 35 EN 60715 Fig 1 4 3 1 2 46 74 120 15 continued ...

Page 11: ... 21 Max three NRS NRR 2 5 units can be connected connection in parallel 7 Level transmitter NRGT 26 4 20 mA with shield connection in terminal box Max three NRS NRR 2 5 units can be connected series connection 8 Central earthing point CEP in control cabinet 9 MIN output contact off delay 3 seconds 0 MAX output contact off delay 3 seconds a Actual value output 4 20 mA Key NRS 2 50 0 5A semi delay 5...

Page 12: ...NRR 2 5 units can be connected connection in parallel 7 Level transmitter NRGT 26 4 20 mA with shield connection in terminal box Max three NRS NRR 2 5 units can be connected series connection 8 Central earthing point CEP in control cabinet 9 MIN output contact off delay 3 seconds 0 MAX output contact off delay 3 seconds a Pump output contact b Actual value output 4 20 mA Key 5 7 9 8 a 0 6 NRS 2 51...

Page 13: ...6 23 in line with the desired switching functions Provide an external 2 5A slow blow fuse for the output contacts Switching off inductive loads produces surges that can have a major adverse effect on the operation of open and closed loop control systems Connected inductive loads must therefore have interference suppression RC combination as per the manufacturer s specifications Tools n Screwdriver...

Page 14: ...1 and NRGT 26 n Route the connecting cable between items of equipment separately from power lines n The level transmitter must be connected to its own dedicated power supply Factory settings Level switch NRS 2 50 n Off delay 3 sec factory set n Input wired as a voltage input for connecting an NRG 21 or NRG 26 21 level electrode n MAX switchpoint AL Hi 80 n MIN switchpoint AL Lo 20 n Calibration va...

Page 15: ...de transmitter The input and function are determined by the setting of code switch c To make changes you can access the code switch as follows s Switch off the supply voltage n Remove the lower terminal strip Fig 4 n Insert a screwdriver on the right and left between the terminal strip and the front frame as shown by the arrows n Release the terminal strip on the right and left sides by turning th...

Page 16: ...NRG 26 21 OFF Input for connecting level transmitter NRGT 26 ON Level switch NRS 2 51 S2 S3 Input for connecting level electrode NRG 21 or NRG 26 21 OFF Input for connecting level transmitter NRGT 26 ON Fill control OFF Discharge control ON grey factory setting Toggle switch white Attention When connecting the NRGT 26 level transmitter please set the upper and lower ends of the measuring range onl...

Page 17: ...d protection is disabled Factory setting 1902 cannot be changed CAL L Calibrate L Only if level electrode NRG 21 or NRG 26 21 is connected Set lower end of measuring range CAL P Calibrate Adjustable between 25 and 100 CAL H Calibrate H Set upper end of measuring range Appears in parameterization mode quit Quit Input is not confirmed done Done Input is confirmed Appears in the event of malfunctions...

Page 18: ...e measuring range only in the transmitter A Lower end of measuring range adjustable B Upper end of measuring range adjustable C Measuring range mm xxx D Inactive range E Maximum installed length at 238 C Set the lower and upper ends of the measuring range for your fill level measurement This produces the measuring range C Please convert the measuring range into percent A B C NRG 2 NRGT 26 D D 37 2...

Page 19: ...knob Turning clockwise increases the value turning anti clockwise reduces the value When your entries are complete Press and hold the button within 3 sec done is displayed After this the display toggles between the parameter and the new value Input is confirmed The display shows the parameter once more If you do not confirm your entry within 3 sec or you do not make any further entries quit is bri...

Page 20: ...easuring range Note n Adjusting the measuring range The advantage of option 2 is that the tank only has to be partially filled Level electrode NRG 2 only Setting the measuring range option 2 Action Indication Function Reduce water level down to lower end of measuring range A Select parameter CAL L After a short time a hexadecimal number flashes Lower end of measuring range is calibrated Press the ...

Page 21: ... Off delay in progress MAX LED lights up red Delay time elapsed MAX output contacts 21 23 closed 22 23 open Setting the MIN MAX switchpoints Select parameter AL Lo enter and save the desired percentage MIN switchpoint is set between 0 100 Select parameter AL Hi enter and save the desired percentage MAX switchpoint is set between 0 100 Level switch NRS 2 51 only Setting pump switchpoints fill contr...

Page 22: ...nction In operating mode Water level between MIN and MAX Select Test parameter Press and hold the pushbutton MAX LED flashes red Off delay in progress MAX LED lights up red for 3 seconds MAX output contact 21 23 closed 22 23 open The MIN and MAX LED are not lit for 1 second MIN output contact 16 18 open 17 18 open MAX output contact 21 23 open 22 23 closed MIN LED flashes red Off delay in progress...

Page 23: ...right flashes 000X The second digit can be entered Repeat the last two steps until the password has been entered in full The entered password is displayed XXXX The password is entered in full Press and hold the pushbutton donE The correct password was entered The parameter may be edited FAiL The wrong password was entered The parameter is still password protected quit Processing time has elapsed S...

Page 24: ...ary Check electrical connection Level transmitter defective measuring current 20 mA Check level transmitter and replace if necessary Check electrical connection E 012 Lower and upper ends of measuring range wrong way round Reset measuring range E 013 MIN switchpoint higher than MAX switch point Reset switchpoints E 097 Walkthrough application error Internal error Replace equipment E 098 Walkthroug...

Page 25: ...ss HF interference using hinged shell ferrite rings Replacing taking the equipment out of service Disposal The equipment must be disposed of in accordance with statutory waste disposal regulations n Switch off the supply voltage and cut off power to the equipment n Remove the upper and lower terminal strips Fig 7 n Insert a screwdriver on the right and left between the terminal strip and the front...

Page 26: ...26 NRS 2 50 NRS 2 51 Installation Operating Manual 819179 05 For your notes ...

Page 27: ...27 NRS 2 50 NRS 2 51 Installation Operating Manual 819179 05 For your notes ...

Page 28: ... AG Bremen Printed in Germany GESTRA AG Münchener Straße 77 28215 Bremen Germany Tel 49 421 3503 0 Fax 49 421 3503 393 E mail info de gestra com Website www gestra com You can find our authorised agents around the world at www gestra com ...

Reviews: