System malfunctions
Indication of system malfunctions using fault codes
Fig. 18
Fault code display
Fault code
Internal
designation
Possible faults
Remedy
E.001
MinCh1Err
Measured value of channel 1 be-
low minimum, potential internal
open circuit
Is the level electrode not immersed?
Check the installation location, replace the
level electrode if necessary
E.002
MinCh2Err
Measured value of channel 2 be-
low minimum, potential internal
open circuit
Is the level electrode not immersed?
Check the installation location, replace the
level electrode if necessary
E.003
MaxCh2Err
Measured value of channel 2
above
maximum, potential internal
open circuit
Replace the level electrode
E.004
Ch1Ch2DiffErr
Over 10% deviation between
channels 1 and 2, internal short
circuit
Replace the level electrode
E.005
MaxCh1Err
Measured value of channel 1
above
maximum, potential internal
open circuit
Replace the level electrode
E.006
MinTSTCh1Err
Measured value channel 1
internal capacity (47pF)
Replace the level electrode
E.007
MaxTSTCh1Err
Measured value channel 1
reference capacity (1nF || 47pF)
Replace the level electrode
E.008
MinTSTCh2Err
Measured value channel 2
internal capacity (47pF)
Replace the level electrode
E.009
MaxTSTCh2Err
Measured value channel 2
reference capacity (1nF || 47pF)
Replace the level electrode
E.010
PWMTSTCh1Err
Measured value channel 1 with
deactivated measurement signal
Replace the level electrode
E.011
PWMTSTCh2Err
Measured value channel 2 with
deactivated measurement signal
Replace the level electrode
OK
!
+
-
1
1
Display of actual value/fault code/limit value, green, 4 digits