18
Attention
Before carrying out the fault diagnosis please check:
Supply voltage:
Is the equipment supplied with the mains voltage specified on the name plate?
Wiring:
Is the wiring in accordance with the wiring diagram?
Troubleshooting
Indication, diagnosis and remedy
Attention
n
Please refer to the installation & operating manuals for LRG 12-2, LRG 16-4,
LRG 16-9, LRG 17-1, LRG 19-1 and TRG 5-.. for further fault-finding and troubleshooting.
Note
If a malfunction occurs in the conductivity switch, MIN and MAX alarms will be triggered
and the equipment is restarted.
Should this happen over and over again, replace the equipment with a new one.
Faults indicated by the seven-segment display
Error code
Error
Remedy
E.001
Temperature sensor defective, temperature
reading too low
Check resistance thermometer, conductivity electrode
LRG 16-9 and, if necessary, replace it with a new one.
Check wiring (short circuit, interruption?)
E.002
Temperature sensor defective, temperature
reading too high
E.005
Conductivity electrode defective, measured
value too low.
Check conductivity electrode and, if necessary, replace
it. Check electrical connection.
E.006
Conductivity electrode defective, measured
value too high.
Check conductivity electrode and, if necessary, replace
it. Check electrical connection.
E.013
MIN switchpoint above MAX switchpoint
Re-adjust the switchpoints.
In the event of a malfunction a MIN and MAX alarm will be triggered.