LRR 1-52, LRR 1-53, URB 55 - Installation & Operating Manual -
850645-01
Configuring the conductivity controller
Setting correction factor C
1.
Establish a
reference reading
.
Once operating temperature is reached, the
conductivity of a sample of water must be
measured.
2.
Tap the
“
Correction factor C
” input field.
3.
Either type in the
correction factor “
C
”
or
Enter the
reference reading
“
X
Ref
” you previ-
ously measured.
Display after entering
reference reading “X
Ref
”
Confirm the calculated correction
factor “
C
”.
Reject the calculated correction factor
“
C
”.
Display when limit is exceeded
If correction factor “
C
” exceeds the
limit 5 1/cm, a warning appears.
In this case, you have no choice but to reject the
calculated correction factor “
C
”.
A value > 5 1/cm indicates heavy
soiling of the conductivity electrode.
The conductivity electrode must be
cleaned.