Instruction Manual COMPACT Arm
5. Subsequently, the hose is mounted on the
ceiling bracket. The rubber band is taken out
over the ceiling bracket, after which the hose
is fixed by means of a clamp. Bending the
edge of the hose is the best way of doing
this, so that the steel spiral is pulled/twisted
up on the bracket. When the hose has been
properly fixed, the rubber band is finally
pulled over the clamp.
6. The hose is mounted on the funnel by
tightening the clamp around the funnel and
the hose. (NB. Remember first to pull the
rubber band over the funnel). When the hose
has been fixed properly, the rubber band is
pulled over the clamp. Subsequently, the
Arm is connected to the complete piping
system.
7.
If the telescopic function cannot remain in the
required position or if there is too much
resistance in the Arm, please adjust the
balancer at the back of the ceiling bracket.
2.1 Mounting of optional equipment
Mounting of the extension arm
Start by fixing the extension arm to a solid wall,
e.g. a concrete wall (applies to 1.0, 2.5 and 4.0
m). (Please refer to the whole dimensions).
At 4 meters, every joint is assembled and then the
Arm is mounted. Next, the spiro pipe is fastened
to the extension arm by means of the enclosed
self-cutting screws. The part between the spiro
pipes is assembled by means of clamps and the
supplied hose. Subsequently, the Arm is attached
to the extension arm.
Mounting of the damper
Is factory-mounted. Contact your dealer.
Mounting of light
The mounting of light and net should have been
taken care of by the factory. Extending the power
cord, which is attached inside the Arm, where it is
to be fixed, makes the connection. Next, the
power cord is connected to the transformer (24V
Æ
220V), which again is connected to the mains.
Light specifications:
Type: Halogen
Power:
50 W 60°
Voltage: 12
V
Recommended Trafo-power:
70 W
2.2 Power connection
For connection of various electrical components
(e.g. light sensor), please refer to the enclosed
documentation for the actual product.
The electrical installation is to be carried out by a
certified electrician.
2.3 Trial run – exact adjustment
After the final mounting, the COMPACT Arm
should be adjusted to the typical working area, for
optimum utilisation of the Arm. Do so by adjusting
the points mentioned in item 2 (3. 4. and 7.)
exactly.
3.0 User instruction – application
For normal use, the Arm is to be self-retaining in
the required position within the working area. The
bracket of the Arm supplies a 360° rotary working
area.
If the equipment has been correctly dimensioned,
the funnel of the Arm should be placed in vertical
position 300-500 mm over the blanks to be
welded. That is just above the pollutant. Thus up
to 99% of the polluting particles will be caught.
Less optimal welding situation.
2.5 & 4 m Extension arm
1 m Extension arm