Contractor:
P.O.:
Engineer:
Project Name:
Unit Tag:
The manufacturer works continually to improve its products. As a result, the design and speci
fi
cations of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signi
fi
es that the equipment is acceptable under the provisions
of the job speci
fi
cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products. York and Af
fi
nity are registered
trademarks of Johnson Controls, Inc., and are used with permission.
Single Speed
Model
gpm
Pressure Drop (psi)
30°F
50°F
70°F
90°F
110°F
012
1.5
0.3
0.3
0.3
0.3
0.3
2.5
1.0
1.0
1.0
1.0
1.0
3.5
1.7
1.7
1.7
1.6
1.6
4.5
2.5
2.4
2.4
2.4
2.3
018
3.0
1.6
1.6
1.5
1.5
1.4
4.0
2.9
2.9
2.8
2.8
2.7
5.0
4.2
4.2
4.1
4.0
3.9
6.0
6.0
5.8
5.7
5.6
5.5
022
3
0.9
0.9
0.8
0.7
0.7
4.5
1.7
1.6
1.5
1.4
1.3
6
2.8
2.7
2.5
2.3
2.2
8
4.7
4.4
4.1
3.9
3.6
030
4
1.3
1.2
1.2
1.1
1.0
6
2.7
2.5
2.4
2.2
2.2
8
4.5
4.2
3.9
3.7
3.4
10
6.8
6.3
5.4
5.4
5.0
036
5
1.0
1.0
0.9
0.8
0.8
7
2.1
1.9
1.8
1.7
1.6
9
3.6
3.3
3.0
2.8
2.6
12
6.3
5.9
5.5
5.1
4.8
042
5
0.8
0.7
0.7
0.7
0.6
8
2.1
2.1
1.9
1.8
1.7
11
4.2
4.1
3.8
3.5
3.3
14
7.6
6.7
6.3
5.8
5.4
048
6
1.1
1.0
1.0
0.9
0.8
9
2.3
2.1
2.0
1.9
1.7
12
3.9
3.7
3.4
3.2
3.0
16
6.7
6.3
5.9
5.5
5.1
060
9
2.4
2.2
2.1
2.0
1.8
12
3.9
3.6
3.4
3.2
2.9
15
5.7
5.3
5.0
4.7
4.3
20
9.5
8.9
8.3
7.8
7.2
070
12
3.0
2.8
2.6
2.4
2.2
15
4.4
4.0
3.8
3.5
3.3
18
6.0
5.5
5.1
4.8
4.4
24
9.7
9.1
8.5
7.9
7.3
2/7/12
Dual Capacity
Model
gpm
Pressure Drop (psi)
30°F
50°F
70°F
90°F
110°F
026
full load
4
1.4
1.3
1.2
1.1
1.0
6
2.8
2.6
2.4
2.3
2.1
8
4.7
4.4
4.1
3.8
3.5
10
7.0
6.6
6.2
5.8
5.3
026
part load
3
0.8
0.7
0.7
0.7
0.6
5
2.0
1.8
1.7
1.6
1.5
7
3.6
3.4
3.2
3.0
2.8
9
5.8
5.5
5.1
4.8
4.4
038
full load
5
1.2
1.2
1.1
1.0
1.0
7
2.2
2.1
1.9
1.8
1.7
9
3.4
3.2
3.0
2.8
2.6
11
4.9
4.6
4.3
4
3.7
038
part load
4
0.9
0.8
0.8
0.7
0.7
6
1.7
1.6
1.5
1.4
1.3
8
2.8
2.6
2.5
2.3
2.1
10
4.2
3.9
3.7
3.4
3.2
049
full load
6
1.2
1.2
1.1
1.0
1.0
9
2.4
2.2
2.1
2.0
1.8
12
3.9
3.6
3.4
3.2
2.9
15
5.7
5.3
5
4.7
4.3
049
part load
5
0.9
0.9
0.8
0.8
0.7
8
2.0
1.8
1.7
1.6
1.5
11
3.4
3.1
2.9
2.8
2.5
14
5.0
4.7
4.4
4.1
3.8
064
full load
8
1.8
1.7
1.6
1.4
1.3
12
3.8
3.5
3.3
3.0
2.8
16
6.5
6.0
5.6
5.2
4.8
20
9.7
9.1
8.5
8.0
7.4
064
part load
6
1.0
0.9
0.9
0.8
0.8
10
2.6
2.5
2.3
2.1
2.0
14
5.0
4.7
4.4
4.1
3.8
18
8.1
7.6
7.1
6.6
6.1
072
full load
12
3.2
3.0
2.8
2.6
2.4
15
4.5
4.2
4.0
3.7
3.4
18
6.0
5.7
5.3
4.9
4.6
21
7.8
7.3
6.8
6.4
5.9
072
part load
10
2.3
2.1
2.0
1.9
1.7
13
3.6
3.3
3.0
2.8
2.6
16
5.0
4.6
4.3
4.0
3.7
19
6.5
6.2
5.8
5.4
5.0
1/26/12
Pressure Drop
SD2500AG 05/21
22
Page _____ of _____
Aston Series
1 - 6 Tons 60Hz