LFP Battery Module – Product Manual
All rights reserved genZ 2020
Issued for Use
Revision
Page
4/03/2020
2.1
14 of 25
SYMPTOM / FAULT
POSSIBLE CAUSE
POSSIBLE SOLUTION
CIRCUIT BREAKER TRIPS
EXCESSIVE DISCHARGE CURRENT
USING A CLAMP METER, CHECK THAT
THE CURRENT BEING DRAWN FROM
THE BATTERY MODULE IS LESS THAN
60AMPS.
REFER TO INFORMATION/WARNING
REGARDING STATE OF CHARGE
EXCESSIVE CHARGE CURRENT
USING A CLAMP METER, CHECK THAT
THE CURRENT BEING SUPPLIED TO THE
BATTERY MODULE IS LESS THAN
60AMPS.
REFER TO INFORMATION/WARNING
REGARDING STATE OF CHARGE
OTHER
RETURN TO GENZ FOR SERVICE
BATTERY MODULE FAILING TO
CHARGE OR HOLD CHARGE
INSUFFICENT CHARGE
VOLTAGE/CURRENT
CHECK FOR FAULTY CHARGER, POOR
CABLING OR LOOSE CONNECTORS
SOLAR OR OTHER CHARGER NOT
CONFIGURED CORRECTLY
REFER TO THE MANUFACTURER OR
THE SOLAR OR MAINS CHARGER
BATTERY CHARGER MAY WELL BE
FAILING TO START A CHARGE CYCLE.
THIS MAY OCCUR WITH SOME SMART
CHARGERS THAT REQUIRE SEEING AT
LEAST SOME VOLTAGE FROM A
BATTERY
CHECK WITH CHARGER
MANUFACTURER OR SUBSTITUTE THE
CHARGER FOR A DIFFERENT TYPE OR
USE A DC POWER SUPPLY SET TO THE
CORRECT CHARGE VOLTAGE AND
CURRENT
OTHER
RETURN TO GENZ FOR SERVICE