background image

Friskluft

Afkast

Udsugning

Indblæsning

Lufttæt samling

100 mm

Lufttæt samling

Til indv. afløb

No water in the water traps:

- drain clogged
- negative pressure resulting in false air

Condensation drain

The units can give off 5-8 litres of condensation in a day. 

Therefore, it is important that the condensation drains 
have been carried out correctly.
The condensation drain pipes must be mounted with the 
necessary gradient from the condensation connections 
on the unit and to the internal drain.

On each condensation drain pipe a water trap must be 

fitted, because there is negative pressure in the chamber 

where the condensation tray is installed.
If the unit is mounted in a cold attic, the condensation 
drain pipes must be insulated so that the condensation in 
the pipes does not freeze up.

However, it is recommended that the water traps are 
installed 
in a heated space to ensure that the water in the water 
traps does not freeze.

If installation problems make it impossible to secure the 
condensate drain pipe from freezing using insulation, 
it will be necessary to mount a thermostat-controlled 
heating coil around the condensate drain pipes.

In connection with checking and replacing filters, it is 

recommended that the water traps are checked and then 

filled with water if necessary.

Insulation of ducts in cold attics

In order to benefit from the unit‘s high heat recovery rate, it 

is necessary that the ducts are insulated properly.

Genvex recommends the following:

Supply air and extract air ducts:

In order to minimise the loss of heat from the duct system 
in cold attics, the supply air and extract air ducts must be 
insulated with a minimum of 100 mm insulation. 
If insulation type A is chosen, it is recommended that 
insulating is done with two layers of 50 mm lamella mat 

finished off with paper or foil on the outside and that the 

joints between the two insulation layers are staggered. 
If the ducts are positioned on the rafter foots, then type 
B can be used. The insulation must always be tightly 
wrapped around the ducts, especially on fresh air and 
exhaust air ducts in cold rooms.

Fresh air and exhaust air ducts:

It is recommended that fresh air and escape air ducts are 
insulated with a minimum of 50 mm insulation. The fresh air 
duct is insulated to prevent warm air in the attic heating up 
the fresh air during the summer. 
Make sure to seal tightly, especially where the ducts are 
led through the roof or out through gables in order to avoid 
condensation damage.

Contact your local supplier for instructions about national 
guidelines concerning insulation.

Premium Preheat range

Isolering af kanaler, alt. A

Isolering af kanaler, alt. B

Forkert isolering af kanaler

Summary of Contents for PREMIUM PREHEAT 250

Page 1: ...INSTALLATION MANUAL PREMIUM PREHEAT 250 300 500 Air air heat recovery ventilation heat pump...

Page 2: ...attics 6 Insulation of ducts in warm rooms 7 Electrical connection 7 Starting up the unit 7 Optimal adjustment of the ventilation system 8 Maintenance of the system 8 Trouble shooting 10 PCB layout 1...

Page 3: ...n tray of the unit to ensure that it flows out freely 6 If the water trap is fitted in a place where there is a risk that the temperature drops below 0 C then an electric heating element with a thermo...

Page 4: ...ted on the top of the unit The electrical box is located on the top of the unit The unit has 2 condensation drains both of which must be connected to a suitable drain The unit must be placed on a soli...

Page 5: ...s installing a silencer between the two rooms It is recommended that the air speeds in the ducts be dimensioned low enough so that there is no noise from the supply air and extract air valves When pos...

Page 6: ...checked and then filled with water if necessary Insulation of ducts in cold attics In order to benefit from the unit s high heat recovery rate it is necessary that the ducts are insulated properly Gen...

Page 7: ...nit and control panel must be a 4 wire min 0 25 mm2 cable with a maximum length of 50 m Starting up the system To achieve optimum operation of the system it must be adjusted with air measuring equipme...

Page 8: ...ting Maintenance of the system Filters When the filter timer reaches the set value for filter change Alarm will show in the screen saver and Chg filter will flash This means that it is time to clean c...

Page 9: ...nger Wash in lukewarm soapy water and rinse using a hand shower if necessary Plastic exchanger No cleaning with fluids including water only careful dust removal from air intake surfaces with a househo...

Page 10: ...been installed correctly No supply air Error Faulty supply air fan Clogged supply air filter Clogged fresh air grill due to dirt and leaves during the fall and snow and ice during the winter Fuse on...

Page 11: ...sors T1 T3 T4 T7 L4 Not in use L5 Not in use L6 Sensors T5 T6 T8 T9 L8 External stop L9 Fan RPM L10 Modulating Pre Reheating L11 0 10V Motorvalve Reheating 0 10V Belimo LM230ASR bypass L16 Not in use...

Page 12: ...fan Supply air Blue Yellow EC fan Extract air 1x230V 50Hz Black Black Blue Blue Yellow green Yellow green Belimo LM230ASR Bypass EC fan Supply air 1x230V 50Hz Electric Reheater Step A 1x230V 50Hz Sol...

Page 13: ...r Fortluft Indbl sning Supply air Zuluft T1 T7 T5 T6 T4 T3 M2 M2 M1 Fordamper Evaporator Verdampfer Kondensator Condenser Verfl ssiger Forvarme Preheater Vorv rme Kompressor Compressor Verdichter HP H...

Page 14: ...nvex The original Danish Ventilation System Genvex is a genuine Danish original We invented the ventilation system more than 40 years ago and we are still ahead of the pack when it comes to developmen...

Reviews: