5.10 Schedule for set points
Item Headline
Factory setting
Configuration area
Date
Date
Date
Date
(5.5) 01 Temperature
21 °C
10 - 30 °C
02 Preheating
OFF
ON / OFF
03 Reheating
OFF
ON / OFF
04 Timer levels 3 and 4
OFF
ON / OFF
05 Change filter
3 months
1 - 12 months
06 Humidity control
OFF
ON / OFF
(5.8) 10 Level 1 Supply air
30 %
0 - 100 %
11 Level 2 Supply air
50 %
0 - 100 %
12 Level 3 and 4 Supply air
75 %
0 - 100 %
13 Level 1 Extract air
30 %
0 - 100 %
14 Level 2 Extract air
50 %
0 - 100 %
15 Level 3 and 4 Extract air
75 %
0 - 100 %
16 Fine tuning (T2)
÷ 3
°C
÷ 5 - 0 °C
17 Timer level 3 and 4
3 hours
1 - 9 hours
18 Filter/stop
OFF
ON / OFF
19 Method of regulation
2
0 - 2
20 Preheating
÷ 3 °C
÷ 15 - 0 °C
21 By pass open
3 °C
1 – 10 °C
22 Regulation water
20 sec.
1 - 250 sec.
23 Regulation electricity
3 min.
1 - 30 min.
24 Frost reduction
0 °C
0 – 10 °C
25 Frost protection
OFF
ON / OFF
26 Frost protection temperature
5 °C
0 - 10 °C
27 Help functions
0
0 - 5
28 System stop
OFF
ON / OFF
29 Turn off bypass
4 °C
0 - 20 °C
30 Modbus Mode
0
0 - 2
31 Modbus Address
1
1 - 247
32 Humidity max. temperature
15 °C
5 - 25 °C
33 Humidity max. value
60 %
35 - 85 %
34 Humidity fan speed
15 %
5 - 30 %
35 Humidity regulating frequency
10 mIn.
1 - 60 min.
36 Not applicable
37 Preheat PI P
5
1-255
38 Preheat PI I
200
1-255
39 Preheat Reg
40
10-120
40 Reheat offset
2
0-20
41 Reheat PI P
5
1-255
42 Reheat PI I
200
1-255
43 Reheat Reg
40
10-120