Installation

Optimal commissioning of the ventilation 

system

Air measuring equipment is necessary for commissioning.

Before starting adjusting the system make sure that the 5 

points in the section commissioning of the unit have been 

carried out. Then start up the unit.

The basic ventilation value adjustment is to be done on 

speed 2. To reduce energy consumption as much as 

possible, start by adjusting the main air volumes to the 

desired air volume by changing the voltage outlet on the 

transformer. 

Then adjust the supply and extract air valves with air 

measuring equipment (when adjusting the supply and 

extract air valves, remember to lock them and to turn the 

guide plate in the supply air valves so the air blows in the 

right direction).

Then measure the main air volumes again and  do the 

finaladjustment of the main air volumes with the fresh and 

extract air dampers (Remember to lock the dampers after 

commissioning).

Maintenance of the unit

Filters:

When the red lamp on the control panel flashes, the filters 

must be changed/cleaned. Stop the unit on the switch 

on the unit or the electrical panel. Open the front cover 

and take out the filter. When the filter has been changed 

or cleaned by shaking it and by removing the worst dirt, 

and mounted again switch on the unit and press the enter 

button on the control panel for 10-15 seconds until the 

Genvex logo starts flashing again and the equipment is 

back in normal operation.

Careful handling of the plates is required. They 

have sharp edges and must not be damaged.

Do not vacuum or clean at high air pressure. It 

will damage the filter!

Remember: do not open the unit, before it has 
been disconnected from the electricity

Condensate drain:

When changing the filter in August/September, before 

outside temperatures fall to 5°C, measure that the 

condensate drain is not blocked by dirt and make sure that 

there is water in the water trap.

Pour 1 litre of water into the condensate tray and make 

sure it runs off without hindrance. If the condensate drain 

does not work, this could lead to water damage in the 

dwelling. 

G4  =  Standard filter 

(Coarse filter class G4)

F5  =  Fine filter (Fine filter class F5)

F7  =  Pollen filter (Fine filter class F7)

Summary of Contents for GE Premium 1/1L

Page 1: ...Version V1 04 0310 GB Installations Manual Active Ventilation Heat pump GES Premium 1 1L GE Premium 1 1L GE Premium 2 GE Premium 3...

Page 2: ...ts in cold loft spaces 6 Insulation of ducts in heated spaces 7 Electrical installation 7 Commissioning of the unit 8 Maintenance of the unit 8 Fault finding 10 Electrical diagram GE Premium serie 11...

Page 3: ...ing when the IMPORTANT IMPORTANT IMPORTANT IMPORTANT IMPORTANT IMPORTANT IMPORTANT IMPORTANT IMPORTANT IMPORTANT temperature drops below 2C 7 Air flow adjustments must be made on both the supply and e...

Page 4: ...ons from the unit cannot be transferred through ceiling and walls and so that the condensate drain with the necessary water trap can be led to an inside drain without danger of freezing in cold weathe...

Page 5: ...commended that the duct system is made of spiral ducting with rubber ring seal fittings in order to provide a tight and durable duct system To achieve a satisfactory low sound level from the unit sile...

Page 6: ...ducts in cold loft spaces In order to high recovery rate of the unit it is necessary to insulate the ducts correctly Supply and extract ducts Supply and extract air duct To minimize heat losses from...

Page 7: ...easuring equipment If you wish to start up the unit before adjustment do as follows Before starting up the unit 1 Make sure that the Genvex unit is correctly mounted and that all ducts are insulated a...

Page 8: ...el flashes the filters must be changed cleaned Stop the unit on the switch on the unit or the electrical panel Open the front cover and take out the filter When the filter has been changed or cleaned...

Page 9: ...heck the two fan wheels for dirt If they are dirty they may be cleaned with a brush bottle washer etc Supply and extract valves Clean the valves by wiping them with a dry cloth Make sure the valve doe...

Page 10: ...living rooms Fault Defect fan Blocked filter Fresh air grill is blocked by dirt and leaves in the autumn or snow and ice in the winter Fuse on control circuit board has blown No extract air from wet r...

Page 11: ...Costumer Yours ref Construct KS Order no Our ref Rev Type GES Premium 1 and 2 EC Date 23 02 20 Page 1 of 1 Serial...

Page 12: ...Premium range Evaporator cooling coil High pressure switch Condenser heating coil MA4 Compressor Control panel MA7 HP Exhaust Air Supply Air T4 T5 T3 T6 T1 T7 T2 Extract Air Fresh Air Counter current...

Page 13: ...13 Notes...

Page 14: ...14 Notes...

Page 15: ...15 Notes...

Page 16: ...m Artiklima bvba B 9220 Hamme Tel 32 0 52 41 25 41 Fax 32 0 52 41 29 66 E Mail info artiklima be Great Britain Total Home Environment Ltd GB Moreton in Marsh GL 56 0JQ Tel 44 0 845 260 0123 Fax 44 0 1...

Reviews: