8
Installation
Optimal commissioning of the ventilation
system
Air measuring equipment is necessary for commissioning.
Before starting adjusting the system make sure that the 5
points in the section commissioning of the unit have been
carried out. Then start up the unit.
The basic ventilation value adjustment is to be done on
speed 2. To reduce energy consumption as much as
possible, start by adjusting the main air volumes to the
desired air volume by changing the voltage outlet on the
transformer.
Then adjust the supply and extract air valves with air
measuring equipment (when adjusting the supply and
extract air valves, remember to lock them and to turn the
guide plate in the supply air valves so the air blows in the
right direction).
Then measure the main air volumes again and do the
finaladjustment of the main air volumes with the fresh and
extract air dampers (Remember to lock the dampers after
commissioning).
Maintenance of the unit
Filters:
When the red lamp on the control panel flashes, the filters
must be changed/cleaned. Stop the unit on the switch
on the unit or the electrical panel. Open the front cover
and take out the filter. When the filter has been changed
or cleaned by shaking it and by removing the worst dirt,
and mounted again switch on the unit and press the enter
button on the control panel for 10-15 seconds until the
Genvex logo starts flashing again and the equipment is
back in normal operation.
Careful handling of the plates is required. They
have sharp edges and must not be damaged.
Do not vacuum or clean at high air pressure. It
will damage the filter!
Remember: do not open the unit, before it has
been disconnected from the electricity
Condensate drain:
When changing the filter in August/September, before
outside temperatures fall to 5°C, measure that the
condensate drain is not blocked by dirt and make sure that
there is water in the water trap.
Pour 1 litre of water into the condensate tray and make
sure it runs off without hindrance. If the condensate drain
does not work, this could lead to water damage in the
dwelling.
G4 = Standard filter
(Coarse filter class G4)
F5 = Fine filter (Fine filter class F5)
F7 = Pollen filter (Fine filter class F7)