background image

Figures 2, 3, 4 & 5 are reprinted with permission from NFPA 72, National Fire Alarm Code®, Copyright ©2010,

National Fire Protection Association, Quincy, MA 02169.  This reprinted material is not the complete and official 

position of the National Fire Protection Association on the referenced subject which is represented only by the 

standard in its entirety.  National Fire Alarm Code® and NFPA 72® are registered trademarks of the National Fire

Protection Association, Inc., Quincy, MA 02169. 

550-0158

Pg. HD-3

In addition to smoke alarms outside of the sleeping areas and in each bedroom,

NFPA 72 requires the installation of a smoke alarm on each additional level of the

dwelling unit, including the basement.  These installations are shown in FIGURE 5.

The living area smoke alarm should be installed in the living room or near the stairway

to the upper lever, or in both locations.  The basement smoke alarm should be

installed in close proximity to the stairway leading to the floor above.  Where installed

on an open-joisted ceiling, the smoke alarm should be placed on the bottom of the

joists.  The smoke alarm should be positioned relative to the stairway so as to 

intercept smoke coming from a fire in the basement before the smoke enters the 

stairway.

FIGURE 3: A SMOKE ALARM MUST BE LOCATED BETWEEN THE SLEEPING

AREA AND THE REST OF THE DWELLING UNIT AS WELL AS IN EACH 

BEDROOM.

In dwelling units with more than one bedroom area or with bedrooms on more than

one floor, more than one smoke alarm is required, as shown in FIGURE 4.

FIGURE 2: A SMOKE ALARM MUST BE LOCATED ON EVERY LEVEL OF

DWELLING UNIT, INCLUDING BASEMENT,  WITHIN EACH SLEEPING ROOM AND

OUTSIDE SLEEPING AREAS.

Where to Locate the Required Smoke Alarms

.  The major threat from fire in a

dwelling unit occurs at night when everyone is asleep.  Persons in sleeping areas can

be threatened by fires in the remainder of the unit; therefore, smoke alarms are best

located in each bedroom and between the bedroom areas and the rest of the unit as

shown in FIGURE 3.

FIGURE 2

FIGURE 3

FIGURE 4

3) On every level of a dwelling unit, including basements

4) On every level of a residential board and care occupancy (small facility),including 

basements and excluding crawl spaces and unfinished attics

5) In the living area(s) of a guest suite

6) In the living area(s) of a residential board and care occupancy (small facility)     

29.5.1.2

Where the area addressed in 29.5.1.1(2) is separated from the 

adjacent living areas by a door, a smoke alarm shall be installed in the area between

the door and the sleeping room, and additional alarms shall be installed on the living

area side of the door as specified by 29.5.1.1 and 29.5.1.3.

29.5.1.3

In addition to the requirements of 29.5.1.1(1) through 29.5.1.1(3), where the

interior floor area for a given level of a dwelling unit, excluding garage areas, is

greater than 93m

2

(1000ft

2

), smoke alarms shall be installed per 29.5.1.3.1 and

29.5.1.3.2.

29.5.1.3.1

All points on the ceiling shall have a smoke alarm within a distance of 9.1m

(30ft) travel distance or shall have an equivalent of one smoke alarm per 46.5m

2

(500ft

2

) is evaluated by dividing the total interior square footage of floor area per level

by 46.5m

2

(500ft

2

).

29.5.1.3.2

Where dwelling units include great rooms or vaulted/cathedral ceilings

extending over multiple floors, smoke alarms located on the upper floor that are

intended to protect the aforementioned area shall be permitted to be considered as

part of the lower floor(s) protection scheme used to meet the requirements of

29.5.1.3.1.

The installation of additional alarms of either the smoke, heat or CO type should

result in a higher degree of protection.  Adding alarms to rooms that are normally

closed off from the required alarms increases the escape time because the fire does

not need to build to the higher level necessary to force smoke out of the closed room

to the required alarms.  As a consequence, it is recommended that the householder

consider the installation of additional fire protection devices.  

However, it should be understood that NFPA 72 does not require additional smoke

alarms over and above those called for in FIGURES 2, 3, 4 and 5  where required

smoke alarms are shown.

FIGURE 4:  IN DWELLING UNITS WITH MORE THAN ONE SLEEPING AREA, A

SMOKE ALARM MUST BE PROVIDED TO PROTECT EACH SLEEPING AREA IN

ADDITION TO SMOKE ALARMS REQUIRED IN BEDROOMS.  

FIGURE 5

FIGURE 5:  A SMOKE ALARM MUST BE LOCATED ON EACH LEVEL IN ADDITION

TO EACH BEDROOM.

IMPORTANT CONSIDERATION

NFPA 72, 2013 Edition, Chapter 29, Section 29.8.1.4(5)(b) states: “Smoke

alarms installed in one- and two-family dwellings shall not remain in service

longer than 10 years from the date of manufacture.”  Smoke alarms should be

replaced for the following reasons:

w

Dust, dirt, and other environmental contaminants can affect your smoke and heat 

alarm over a prolonged period.

w

Fast changing industry consensus standards and codes on all smoke and heat 

alarms make it advisable to periodically upgrade your devices to maximize life 

safety.

w

Assurance that your smoke and heat alarm needs are kept abreast with the 

constantly improving electronic technology.

w

Smoke and heat alarms are recognized as one of the lowest cost ways to protect 

dwelling inhabitants against the danger of fire(s).  It makes good common sense to 

periodically replace and update your smoke alarm that contributes so much to life 

safety.

MOUNTING LOCATION

This heat alarm can be mounted on a ceiling or wall with equal efficiency in either

location.

w

Ceiling location

-heat alarm should be mounted at least 4 inches (100 mm) from a 

wall.   

w

Wall location

-locate the top of the heat alarm not less than 4 inches (100 mm) or 

more than 12 inches (300mm) from the ceiling.  

FIGURE 6

FIGURE 6: RECOMMENDED HEAT ALARM MOUNTING LOCATIONS
The placement of the alarm is critical if maximum speed of fire detection is desired.

Thus, a logical location for a alarm is the center of the ceiling.  At this location, the

alarm is closest to all areas of the room.

Summary of Contents for HD135 Series

Page 1: ...ds against which heat detection may not be effective such as smoking in bed explosions when a closed door separates the heat alarm from the source of the fire etc The ultimate responsibility for fire protection rests solely on you Installing heat alarms is just the first step in protecting your family from fires You also must reduce the chances that fires will start in your home and increase your ...

Page 2: ... IT SHOULD BE USED INSIDE A SINGLE FAMILY HOME OR ONE APARTMENT OF A MULTI FAMILY BUILDING IN A MULTI FAMILY BUILDING THE UNIT MAY NOT PROVIDE EARLY WARNING FOR RESIDENTS IF IT IS PLACED OUTSIDE OF THE RESIDENTIAL UNITS SUCH AS ON OUTSIDE PORCHES IN CORRIDORS LOBBIES BASEMENTS OR IN OTHER APARTMENTS IN MULTI FAMILY BUILDINGS EACH RESIDENTIAL UNIT SHOULD HAVE ALARMS TO ALERT THE RESIDENTS OF THAT U...

Page 3: ... per 29 5 1 3 1 and 29 5 1 3 2 29 5 1 3 1 All points on the ceiling shall have a smoke alarm within a distance of 9 1m 30ft travel distance or shall have an equivalent of one smoke alarm per 46 5m2 500ft2 is evaluated by dividing the total interior square footage of floor area per level by 46 5m2 500ft2 29 5 1 3 2 Where dwelling units include great rooms or vaulted cathedral ceilings extending ove...

Page 4: ... NOTICE THE WIRING TO BE USED SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF ARTICLE 300 3 B 210 OF THE NATIONAL ELECTRICAL CODE NFPA 70 WIRE INSTALLATION SHOULD BE PERFORMED ONLY BY A LICENSED ELECTRICIAN WIRING ONE HEAT ALARM 1 Run a minimum of 16 gauge 2 conductor cable plus ground 3 wires to the alarm junction box from a power supply Use ANSI UL Listed Class 1 wire NOTICE THE WIRING TO BE USED ...

Page 5: ...1 or e mail FP_RMA gentex com to obtain a RMA Number from our Customer Service Department 3 Place the heat alarm up to the mounting plate rotating it clockwise until alarm firmly snap locks into place Keep the heat alarm parallel to the mounting plate so upper and lower tabs on the plate seat correctly into the heat alarm ROTATE ALARM TO UPRIGHT POSITION WORK CONNECTOR WIRES BACK THROUGH HOLE IN A...

Page 6: ... WARRANTIES CANNOT BE DISCLAIMED SUCH IMPLIED WARRANTIES SHALL APPLY ONLY FOR THE WARRANTY PERIOD SPECIFIED ABOVE PLEASE NOTE THAT SOME STATES COUNTRIES AND PROVINCES DO NOT ALLOW LIMITATION ON HOW LONG AN IMPLIED WARRANTY OR CONDITION LASTS SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU EXCEPT AS PROVIDED IN THIS WARRANTY AND TO THE EXTENT PERMITTED BY LAW GENTEX WILL NOT BE LIABLE FOR ANY DIRECT S...

Reviews: