Figures 2, 3, 4 & 5 are reprinted with permission from NFPA 72, National Fire Alarm Code®, Copyright ©2010,
National Fire Protection Association, Quincy, MA 02169. This reprinted material is not the complete and official
position of the National Fire Protection Association on the referenced subject which is represented only by the
standard in its entirety. National Fire Alarm Code® and NFPA 72® are registered trademarks of the National Fire
Protection Association, Inc., Quincy, MA 02169.
550-0158
Pg. HD-3
In addition to smoke alarms outside of the sleeping areas and in each bedroom,
NFPA 72 requires the installation of a smoke alarm on each additional level of the
dwelling unit, including the basement. These installations are shown in FIGURE 5.
The living area smoke alarm should be installed in the living room or near the stairway
to the upper lever, or in both locations. The basement smoke alarm should be
installed in close proximity to the stairway leading to the floor above. Where installed
on an open-joisted ceiling, the smoke alarm should be placed on the bottom of the
joists. The smoke alarm should be positioned relative to the stairway so as to
intercept smoke coming from a fire in the basement before the smoke enters the
stairway.
FIGURE 3: A SMOKE ALARM MUST BE LOCATED BETWEEN THE SLEEPING
AREA AND THE REST OF THE DWELLING UNIT AS WELL AS IN EACH
BEDROOM.
In dwelling units with more than one bedroom area or with bedrooms on more than
one floor, more than one smoke alarm is required, as shown in FIGURE 4.
FIGURE 2: A SMOKE ALARM MUST BE LOCATED ON EVERY LEVEL OF
DWELLING UNIT, INCLUDING BASEMENT, WITHIN EACH SLEEPING ROOM AND
OUTSIDE SLEEPING AREAS.
Where to Locate the Required Smoke Alarms
. The major threat from fire in a
dwelling unit occurs at night when everyone is asleep. Persons in sleeping areas can
be threatened by fires in the remainder of the unit; therefore, smoke alarms are best
located in each bedroom and between the bedroom areas and the rest of the unit as
shown in FIGURE 3.
FIGURE 2
FIGURE 3
FIGURE 4
3) On every level of a dwelling unit, including basements
4) On every level of a residential board and care occupancy (small facility),including
basements and excluding crawl spaces and unfinished attics
5) In the living area(s) of a guest suite
6) In the living area(s) of a residential board and care occupancy (small facility)
29.5.1.2
Where the area addressed in 29.5.1.1(2) is separated from the
adjacent living areas by a door, a smoke alarm shall be installed in the area between
the door and the sleeping room, and additional alarms shall be installed on the living
area side of the door as specified by 29.5.1.1 and 29.5.1.3.
29.5.1.3
In addition to the requirements of 29.5.1.1(1) through 29.5.1.1(3), where the
interior floor area for a given level of a dwelling unit, excluding garage areas, is
greater than 93m
2
(1000ft
2
), smoke alarms shall be installed per 29.5.1.3.1 and
29.5.1.3.2.
29.5.1.3.1
All points on the ceiling shall have a smoke alarm within a distance of 9.1m
(30ft) travel distance or shall have an equivalent of one smoke alarm per 46.5m
2
(500ft
2
) is evaluated by dividing the total interior square footage of floor area per level
by 46.5m
2
(500ft
2
).
29.5.1.3.2
Where dwelling units include great rooms or vaulted/cathedral ceilings
extending over multiple floors, smoke alarms located on the upper floor that are
intended to protect the aforementioned area shall be permitted to be considered as
part of the lower floor(s) protection scheme used to meet the requirements of
29.5.1.3.1.
The installation of additional alarms of either the smoke, heat or CO type should
result in a higher degree of protection. Adding alarms to rooms that are normally
closed off from the required alarms increases the escape time because the fire does
not need to build to the higher level necessary to force smoke out of the closed room
to the required alarms. As a consequence, it is recommended that the householder
consider the installation of additional fire protection devices.
However, it should be understood that NFPA 72 does not require additional smoke
alarms over and above those called for in FIGURES 2, 3, 4 and 5 where required
smoke alarms are shown.
FIGURE 4: IN DWELLING UNITS WITH MORE THAN ONE SLEEPING AREA, A
SMOKE ALARM MUST BE PROVIDED TO PROTECT EACH SLEEPING AREA IN
ADDITION TO SMOKE ALARMS REQUIRED IN BEDROOMS.
FIGURE 5
FIGURE 5: A SMOKE ALARM MUST BE LOCATED ON EACH LEVEL IN ADDITION
TO EACH BEDROOM.
IMPORTANT CONSIDERATION
NFPA 72, 2013 Edition, Chapter 29, Section 29.8.1.4(5)(b) states: “Smoke
alarms installed in one- and two-family dwellings shall not remain in service
longer than 10 years from the date of manufacture.” Smoke alarms should be
replaced for the following reasons:
w
Dust, dirt, and other environmental contaminants can affect your smoke and heat
alarm over a prolonged period.
w
Fast changing industry consensus standards and codes on all smoke and heat
alarms make it advisable to periodically upgrade your devices to maximize life
safety.
w
Assurance that your smoke and heat alarm needs are kept abreast with the
constantly improving electronic technology.
w
Smoke and heat alarms are recognized as one of the lowest cost ways to protect
dwelling inhabitants against the danger of fire(s). It makes good common sense to
periodically replace and update your smoke alarm that contributes so much to life
safety.
MOUNTING LOCATION
This heat alarm can be mounted on a ceiling or wall with equal efficiency in either
location.
w
Ceiling location
-heat alarm should be mounted at least 4 inches (100 mm) from a
wall.
w
Wall location
-locate the top of the heat alarm not less than 4 inches (100 mm) or
more than 12 inches (300mm) from the ceiling.
FIGURE 6
FIGURE 6: RECOMMENDED HEAT ALARM MOUNTING LOCATIONS
The placement of the alarm is critical if maximum speed of fire detection is desired.
Thus, a logical location for a alarm is the center of the ceiling. At this location, the
alarm is closest to all areas of the room.