Gentex 7109CS Installation Instructions Manual Download Page 3

Figure 4

Figures 1, 2, 3, & 4 are reprinted with permission from NFPA 72, National Fire Alarm Code®,

Copyright ©2002, National Fire Protection Association, Quincy, MA 02169. This reprinted

material is not the complete and official position of the National Fire Protection Association on

the referenced subject which is represented only by the standard in its entirety. National Fire

Alarm Code® and NFPA 72® are registered trademarks of the National Fire Protection

Association, Inc., Quincy, MA 02169.

Figure 3: IN DWELLING UNITS WITH MORE THAN ONE SLEEPING

AREA, A SMOKE ALARM MUST BE PROVIDED TO PROTECT

EACH SLEEPING AREA IN ADDITION TO SMOKE ALARMS

REQUIRED IN BEDROOMS.

In addition to smoke alarms outside of the sleeping areas and in

each bedroom, NFPA 72 requires the installation of a smoke alarm on

each additional level of the dwelling unit, including the basement.

These installations are shown in Figure 4. The living area smoke

alarm should be installed in the living room or near the stairway to the

upper level, or in both locations. The basement smoke alarm should

be installed in close proximity to the stairway leading to the floor

above. Where installed on an open-joisted ceiling, the smoke alarm

should be placed on the bottom of the joists. The smoke alarm should

be positioned relative to the stairway so as to intercept smoke coming

from a fire in the basement before the smoke enters the stairway.

Figure 1:

A SMOKE ALARM MUST BE LOCATED ON EVERY

LEVEL OF DWELLING UNIT, INCLUDING BASEMENT, WITHIN

EACH SLEEPING ROOM AND OUTSIDE SLEEPING AREAS.

Where to Locate the Required Smoke Alarms

. The major threat

from fire in a dwelling unit occurs at night when everyone is asleep.

Persons in sleeping areas can be threatened by fires in the remainder

Figure 1

Figure 2

Figure 3

550-0094

Page 7-3

Figure 4: A SMOKE ALARM MUST BE LOCATED ON EACH LEVEL

IN ADDITION TO EACH BEDROOM.

IMPORTANT CONSIDERATION

NFPA 72, 2010 Edition, Chapter 29, Section 29.8.1.4(5)(b)

states: “Smoke alarms installed in one- and two-family dwellings

shall not remain in service longer than 10 years from the date of

manufacture.” Smoke alarms should be replaced for the

following reasons:

Dust, dirt, and other environmental contaminants can affect your

smoke alarm over a prolonged period.

Fast changing industry consensus standards and codes on all

smoke alarms make it advisable to periodically upgrade your device

to maximize life safety.

Assurance that your smoke alarm needs are kept abreast with the

constantly improving electronic technology.

Smoke alarms are recognized as one of the lowest cost ways to

protect dwelling inhabitants against the danger of fire(s). It makes

good common sense to periodically replace and update your smoke

alarm that contributes so much to life safety.

MOUNTING LOCATION

Ceiling location (CS & CSX only) - smoke alarm should be mounted

as close as possible to the center of a hallway or room.

Wall location-locate the top of the smoke alarm not more than 12

inches from the ceiling and must be within 16 feet of pillow. Observe

Figure 2: A SMOKE ALARM MUST BE LOCATED BETWEEN THE

SLEEPING AREA AND THE REST OF THE DWELLING UNIT AS

WELL AS IN EACH BEDROOM.

In dwelling units with more than one bedroom area or with

bedrooms on more than one floor, more than one smoke alarm is

required, as shown in Figure 3.

other health and supervisory care and retirement homes. Please

refer to NFPA 101,The Life Safety Code, and NFPA 72 for smoke

alarm requirements for fire protection in buildings not defined as

"households."

Installing smoke alarms may make you eligible for lower insurance

rates, but

smoke alarms are not a substitute for insurance.

Visual signals are only one method of alerting the hearing impaired

to a fire. The visual signal may not awaken all hearing impaired

individuals. The visual signal must be in the line of sight of the

individual to be seen and effective. Home owners and renters should

continue to insure their lives and property.

PLACEMENT OF SMOKE ALARMS

THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE

WITH THE NATIONAL FIRE PROTECTION ASSOCIATION'S

STANDARD 72 (National Fire Protection Association, Batterymarch

Park, Quincy, MA 02269).

For your information, the National Fire Protection Association's

Standard 72, reads as follows:

NFPA 72, 2010 Edition, Chapter 29, Section 29.5.1 Required

Detection, states the following:

29.5.1.1

Where required by applicable laws, codes or standards for a

specific type of occupancy, approved single and multiple-station

smoke alarms shall be installed as follows:

1) In all sleeping rooms and guest rooms

2) Outside of each separate dwelling unit sleeping area, within 6.4m

(21ft) of any door to a sleeping room, the distance measured along a

path of travel

3) On every level of a dwelling unit, including basements

4) On every level of a residential board and care occupancy (small

facility), including basements and excluding crawl spaces and

unfinished attics

5) In the living area(s) of a guest suite

6) In the living area(s) of a residential board and care occupancy

(small facility)

29.5.1.2

Where the area addressed in 29.5.1.1(2) is separated from

the adjacent living areas by a door, a smoke alarm shall be installed in

the area between the door and the sleeping room, and additional

alarms shall be installed on the living area side of the door as

specified by 29.5.1.1 and 29.5.1.3.

29.5.1.3

In addition to the requirements of 29.5.1.1(1) through

29.5.1.1(3), where the interior floor area for a given level of a dwelling

unit, excluding garage areas, is greater than 93m

2

(1000ft

2

), smoke

alarms shall be installed per 29.5.1.3.1 and 29.5.1.3.2.

29.5.1.3.1

All points on the ceiling shall have a smoke alarm within a

distance of 9.1m (30ft) travel distance or shall have an equivalent of

one smoke alarm per 46m

2

(500ft

2

) is evaluated by dividing the total

interior square footage of floor area per level by 46m

2

(500ft

2

).

29.5.1.3.2

Where dwelling units include great rooms or vaulted/

cathedral ceilings extending over multiple floors, smoke alarms

located on the upper floor that are intended to protect the aforemen-

tioned area shall be permitted to be considered as part of the lower

floor(s) protection scheme used to meet the requirements of

29.5.1.3.1.

The installation of additional alarms of either the smoke, heat or

CO type should result in a higher degree of protection. Adding alarms

to rooms that are normally closed off from the required alarms

increases the escape time because the fire does not need to build to

the higher level necessary to force smoke out of the closed room to

the required alarms. As a consequence, it is recommended that the

householder consider the installation of additional fire protection

devices. However, it should be understood that NFPA 72 does not

require additional smoke alarms over and above those called for in

Figures 1, 2, 3 and 4 where required smoke alarms are shown.

of the unit; therefore, smoke alarms are best located in each bedroom

and between the bedroom areas and the rest of the unit as shown in

Figure 2.

Summary of Contents for 7109CS

Page 1: ...BIENT TEMPERATURE RANGE 40OF to 100OF ALARM HORN RATING 90dBA at 10ft Under normal conditions the light generated by the pulsing infrared LED is not seen by the light sensor as it is positioned out of the direct path of the light beam When smoke enters the sensing chamber light from the pulsing LED light source is reflected by the smoke particles onto the photodiode light sensor At the first sight...

Page 2: ...re detection and smoke alarm systems necessary to protect persons and property in non residential buildings such as warehous es or other large industrial or commercial buildings It alone is not a suitable substitute for complete fire detection systems designed to protect individuals in hotels and motels dormitories hospitals or 550 0094 Page 7 2 limited life and devices that don t work cannot prot...

Page 3: ...y Code and NFPA 72 for smoke alarm requirements for fire protection in buildings not defined as households Installing smoke alarms may make you eligible for lower insurance rates but smoke alarms are not a substitute for insurance Visual signals are only one method of alerting the hearing impaired to a fire The visual signal may not awaken all hearing impaired individuals The visual signal must be...

Page 4: ...ing bracket before it s secured to the junction box WIRING ONE SMOKE ALARM 7109CS CSX 7139CS CSX ONLY 1 Run a minimum of 16 gauge 2 conductor cable plus ground 3 wires to the device junction box from a power supply Smoke alarms should be run on their own dedicated circuit Use UL listed Class 1 wire NOTE The wiring to be used shall be in accordance with the provisions of Article 300 3 b of the Nati...

Page 5: ...ed drill two 3 16 holes insert the screw anchors and mount the plate to wall using screws 4 Mount the smoke alarm to the bracket as illustrated in Figure 13 5 Use the enclosed cord retainer clamp as illustrated in Figure 14 to insure the unit is not accidentally disconnected Place smoke alarm up to mounting plate rotating it to about 10 00 o clock then rotate it clockwise to 12 00 It should snap l...

Page 6: ...ectrical power cord to smoke alarm and remove battery 3 Select three 3 standard size wash buckets and fill them each with one gallon of normal tap water distilled or de ionized treated water is recommended as a final rinse if water is extremely hard in your area 4 Add 1 8 cup of Ivory dishwashing liquid to first bucket of water mix thoroughly Place one dirty smoke alarm into soap water mixture Fig...

Reviews: