25
FUNCTION GROUP 4 –
Digital Display Modes
Function
No. Description
Range/Code
Factory
Setting
4.00
Display Mode
0000:
Frequency
0001:
RPM
(1)
0002:
Custom Units
0000
4.01
Custom Units Significant Digits
0 – 9999
100
4.02
Custom Units Display
0000:
Whole Numbers
0001:
One Decimal Place
0002:
Two Decimal Places
0003:
Three Decimal Places
0000
4.03
Display in Stop Mode
0000:
Displays Last Run Setting
0001:
Displays "StoP"
0002:
Displays "0000"
0000
4.04
Motor Current Display
(2), (3)
0000:
Disabled
0001:
Enabled
0000
4.05 Motor
Voltage
Display
(2), (3)
0000:
Disabled
0001:
Enabled
0000
4.06
Bus Voltage Display
(2), (3)
0000:
Disabled
0001:
Enabled
0000
Notes: (1)
Based on 4-pole motor.
(2)
The Display Key is used to toggle between displays. See Figure 18, on page
19.
(3)
If Motor Current Display is enabled, the display will show "XX.XA". If Motor Voltage Display is enabled, the
display will show "XXXu". If Bus Voltage Display is enabled, the display will show "XXXU".
FUNCTION GROUP 5 –
Onboard Multi-Function Output Relay Operating Mode
Function
No. Description
Range/Code
Factory
Setting
5.00
Relay Operation Mode
0000:
Run
0001:
Fault
(1)
0002:
Target Frequency
(Function No. 5.01 ± Function No. 5.02)
0003:
Frequency Threshold Level
(> Function No. 5.01 – Function No. 5.02)
(2)
0004:
Frequency Threshold Level
(< Function No. 5.01 + Function No. 5.02)
(3)
0005:
I
2
t or I•t Fault
0006:
Load Loss (See Function No. 5.03)
0000
5.01
Frequency Reached (Hz)
0.00 – 240.0
0.00
5.02
Frequency Bandwidth (± Hz)
0.00 – 30.00
1.00
5.03
Load Loss Threshold
(4)
(% Motor Current)
(Set by Function No. 0.01)
25 – 90
60
Note: (1)
The Multi-Function Output Relay Contacts will change state due to all Faults and Recovered Faults.
(2)
The Multi-Function Output Relay will activate above the setting in Function No. 5.01 and deactivate below the
setting in Function No. 5.01 minus the setting in Function No. 5.02.
(3)
The Multi-Function Output Relay will activate
below the setting in Function No. 5.01 and deactivate above the setting in Function No. 5.01 plus the setting in
Function No. 5.02.
(4)
The Load Loss Threshold function is not functional during acceleration/deceleration or Stop
Mode.
Summary of Contents for KBMK Series
Page 9: ...9 FIGURE 3 COVER LAYOUT I FIGURE 4 DRIVE LAYOUT...
Page 50: ...50 NOTES...
Page 51: ...51 NOTES...