used as directed,
DAX
will not harm aluminum or steel.
Any problem arising out of the use of another cleaning
agent will void the warranty. Do not use detergents that
are corrosive or abrasive or detergents containing
chlorine or ammonia.
SERVICE
The Air Cleaner when operating normally will have
the fan running and the performance indicator light
ON
. If
this is not the case the see the Troubleshooting Guide for
probable causes and remedies.
Testing For High Voltage At Power Board
For the following test you will need to have the hinged
cover open with the
collecting cells out of the unit
.
1. Remove the cover panel to the power box. Push a
screwdriver into the slot to defeat the interlock switch
and turn the Air Cleaner
ON
.
2. With a long shafted screwdriver, with a plastic handle,
short between the grounded side of the power box
and the HV1 terminal of the power board.
3. If you draw a good spark, there is high voltage from
the power board.
Measuring High Voltage At Power Board
A high voltage meter capable of measuring up to
10,000 VDC is required to test the voltage.
1. The Air Cleaner should be
ON
with the cells installed
and the cell access door closed. The Air Cleaner
should be on at least 5 minutes to allow voltage to
stabilize.
2. Open the hinged cover. Remove the cover panel from
power box and leave the hinged cover open.
3. Connect the ground of the high voltage meter to
ground stud in the power box.
4. Turn the Air Cleaner
ON
, and defeat the interlock
switch.
5. Check terminals HV1 and HV2 on the power board to
determine if voltage is present. See Fig. 5 for values..
5. If no voltage is present, remove both cells from the
Air Cleaner.
a. Check the voltage at HV1 and HV2 again.
b. If voltage is present, the problem is with one of
the cells or the wiring to the copper contacts.
c. Check the condition of the copper contacts.
d. If the contacts are not bent, replace one cell and
retest voltage. If the performance light come
ON
,
test the other cell. If the problem is with a cell,
see the Troubleshooting Guide.
e. If there is no voltage with both cells removed,
check the power board, system switch and
transformer to make sure that they are
functioning correctly.
6. If there is voltage present, but the performance light
does not come on, replace the light.
7. High voltage can be adjusted with the high voltage
potentiometer if required.
Replacing A Performance Light
Before replacing the performance light, turn
OFF
power to the Air Cleaner at the source.
1. Lower the cover and remove the power box cover
panel.
2. Disconnect the performance light wiring connected to
the neon lamp terminals (P5 and P6) on the power
board. Carefully cut the wire ties from the wire
bundle.
3. Push the light out through front of power box.
4. Push the new light into the power box.
5. Connect the wiring to the neon lamp terminals on the
power board, P5 and P6. Route the wires away from
the high voltage section of the power board.
6. Replace cover panel and close the cover.
7. Return power to Air Cleaner. Test light.
Replacing A Power Board
Before replacing the power board, turn
OFF
power to
the Air Cleaner at the source.
1. Lower the cover and remove the power box cover
panel.
2. Disconnect wiring from the neon lamp, HV1, HV2 and
24 V terminals. Make note of position of wires.
3. Remove the hex nuts from the power board.
4. Remove the power board from the studs.
5. Place the new board onto studs with the 24 volt input
close to the transformer.
6. Replace the hex nuts removed in Step 3. Ensure the
star washer is in place over the nut at the ground
location under the power board. For proper grounding
the washer must be located under the power board.
7. Reconnect wiring to neon lamp, HV1, HV2, and 24 V
terminals on the new power board. See Fig. 5.
5
WARNING
Electronic Air Cleaners use high voltage (low
amperage). Only trained personnel should perform
service.
USE CAUTION!
Electric shock can cause
injury or death.
CAUTION
For most troubleshooting the cells should be
removed from the Air Cleaner.
A short in one of the
cells will cause the power board to shutdown and the
performance light will stay off. Unless otherwise
directed remove the cells from the unit when testing.
WARNING
When performing LIVE tests in the power box
NEVER
touch any parts other then what are mentioned in the
tests. Components carry dangerous voltages and
extreme care must be taken.