background image

WARNING!    Do  not  set  relative  humidity  too  high  during  cold 
weather.  Over  humidification  can  result  in  condensation, 
structural damage and mold.  Condensation within a building's 
structure can cause loss of structural strength.  Condensation 
can also enable mold and mildew growth resulting in personal 
injury and damage to building structure and contents.

RESIDENTIAL AIR TREATMENT PRODUCTS

Manual humidistat/dehumidistat

control

R

II. APPLICATION 

The  MHX3  control  provides  low  voltage  control  of  most 
humidifiers.  The humidistat uses a SPDT switch and is designed 
for wall mounting in the living area or mounting on the return air 
duct.
RANGE: 10% to 85% RH ELECTRICAL RATING: 30 VAC, 60 VA

OPERATING MODES

The  MHX3  can  be  configured  for  operation  as  a  standard 
humidistat  or  dehumidistat.    When  using  this  product  as  a 
standard humidstat terminals C and NO must be used. Use MHX3 
face plate for the humidistat version. When using this product as a 
dehumidistat terminals C and NC must be used. Use DHX3 face 
plate for the dehumidistat version.

I. SAFETY
WARNING!  Improper electrical wiring can result in fire, 
failure or loss of humidity control.  Disconnect electrical 
power before installing and servicing. Failure to disconnect 
electrical power may result in injury or death.  All local 
building and electrical codes must be followed.

The MHX3 humidistat must be installed by a qualified technician.  
Failure to properly install the MHX3C may result in property 
damage or personal injury. 
Homeowners must read instructions and understand the operation 
of the MHX3 and the humidifier(s) it controls.  
Improper operation can result in over or under humidification.  
Over humidification can result in condensation, structural damage 
and mold.  Condensation within a building's structure can cause 
loss of structural strength.  Condensation can also enable mold 
and mildew growth resulting in personal injury and damage to 
building structure and contents.
Safety questions regarding the MHX3 may be directed to General 

Filters, Inc. Toll free (866) 476-5101

MHX3

WIRING DIAGRAMS

DIAGRAM 1

WIRING 24V. BYPASS HUMIDIFIER

HUMIDIFIER 24V.

SOLENOID VALVE

OR 24V. DRUM MOTOR

727-58

24 V. TRANSFORMER

(OMIT IF POWER SUPPLY

IS 20-30 VAC)

120V. POWER SUPPLY 

SWITCHED WITH FURNACE OPERATION

HMX3

 Humidistat

USE TERMINALS C AND NO FOR HUMDISTAT

DIAGRAM 2 WIRING HIGH LIMIT HUMIDISTAT WITH ELITE STEAM HUMIDIFIER

STEAM HUMIDIFIER

CONTROL

 MODULE

HUMIDISTAT

N2

GND

N1

AB

AB

GND

IN

NO

C

NC

C

NO

GND

24V

DIAGRAM 3

WIRING 120V. 1137/1000 POWER HUMIDIFIER

HUMIDIFIER CONTROL LEADS

(YELLOW WIRES)

HUMIDISTAT

HUMIDIFIER 24V AUX POWER

(RED WIRES)

(NOT USED, ATTACH WIRE 

NUTS TO EACH LEAD)

DO NOT TOUCH TOGETHER!

110V SWITCHED WITH FURNACE HEATING CYCLE

L1

N

G

HUMIDIFIER

POWER CORD

DIAGRAM 4

WIRING 120V. 1137/1000 POWER HUMIDIFIER

HUMIDIFIER 24V AUX POWER

(RED WIRES)

(NOT USED, ATTACH WIRE 

NUTS TO EACH LEAD)

DO NOT TOUCH TOGETHER!

110V CONSTANT VOLTAGE

HUMIDIFIER CONTROL LEADS

(YELLOW WIRES)

HUMIDISTAT

110V SWITCHED WITH 

FURNACE HEATING CYCLE

FIELD SUPPLIED RELAY

24V COIL, N.O. 5A MIN.

L1

N

L1

N

G

HUMIDIFIER

POWER CORD

727-58

24 V. TRANSFORMER

(OMIT IF POWER

SUPPLY IS 20-30 VAC)

TROUBLESHOOTING -- Humidistat Version

SYMPTOM

DIAGNOSTIC STEPS

Humidifier turns 
on and off 
repeatedly

1. If mounted on wall, verify wire clearance hole in wall is sufficiently                   
    insulated to preven drafts from affecting the humidistat.
2. If mounted on return air duct, verify humidistat is at least 24”      
    upstream of humidifiers air discharge.

Humidifier 
operates 
continuously

1. When the humidity in the home is less than the knob setting on  
    the humidistat the stat will operate the humidfier until the humidity  
    is higher. Reduce knob setting.
2. Verify function of solenoid valve.

No humidifier 
operation in “ON” 
mode

1. Set the thermostat to operate both furnace burner and blower.   
    Operation may be necessary for system power.
2. Verify terminals 2 and 3 are used on the humidistat. These are the  
    contacts for humidification.
3. Check voltage at at terminals 2 and 3. There should be no voltage  
    for an Elite Steam or 1137/1000 power humidifier. Voltage should  
    be 20-30 VAC from most others.
4. Verify humidifier operation by bypassing the humidistat.

Ideal humidity is 
not achieved

1. Technical fault with humidifier. Check water supply, electrical    
    connnections and condition of the evaporator pad. Verify metering  
    orifice at the solenoid valve is not obstructed.
2. Humidifier run time is too short. Switch water supply to hot water if  
    appropriate (use copper tubing).
3. Excess air infiltration. Seal sources of air loss.
4. Humidifier is undersized. Switch water supply to hot water if    
    appropriate (use copper tubing). Add additional unit(s) or  

 

    replace existing unit with a larger unit.

USE TERMINALS C AND NO

 FOR HUMDISTAT

DIAGRAM 5

1300 DEHUMIDIFIER

HUMIDISTAT

DH

G2

S1

S2

G1

C

W

Y

D

GENERALAIRE 1300

DEHUMIDIFIER

FORM NO MHX3-06 REV C

WALL MOUNT VERSION

FIG. 1

USE TERMINALS C AND NO FOR HUMDISTAT

USE TERMINALS C AND NO FOR HUMDISTAT

USE TERMINALS C AND NC FOR DEHUMDISTAT

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

III.  INSTALLATION INSTRUCTIONS - PRECAUTIONS

The installer must be a qualified technician.  Disconnect electrical
power before begining installation.  Do not install the humidistat 
on the warm air duct.  Conduct a thorough checkout before leaving
the installation.

WALL MOUNT INSTRUCTIONS - Humidistat/Dehumidistat 
versions

 

1.  Choose a location for the MXH3 about five feet above the floor 
     on an inside wall with average room temperature and relative
     humidity conditions.
2.  Drill a small hole in the wall and run low voltage wiring to the
     location chosen.  Pull about 6” of wire through the hole.  
     Use the entire mounting gasket (both inside and outside
     portions) to seal the wall opening or use foam tape to prevent 
     drafts from affecting the humidistat operation. (see fig 3.) 
3.  Remove the knob on the humidistat.  Squeeze the top and 
     bottom of the base to release the face of the humidistat.
4.  Mount the base horizontally over the wires.  Attach directly to 
     the wall, using the two screws provided in the slotted holes.
5.  Connect the wires to the screw terminals on the control assembly
     as shown in wiring DIAGRAMS 1-5  Replace face and Knob. 

DUCT MOUNTING ON THE RETURN AIR - WALL BASE
Humidistat/Dehumidistat versions (optional)

Do not install the humidistat on the warm air duct or within 48”
of UV light.
1.  Locate the humidistat at least  24” upstream of the humidifier or 
     bypass on the return air duct.  Avoid areas of direct radiation like
     secondary heat exchanger in the fan compartment.
2.  Cut a square in the duct 2-1/4” wide and 1-3/4” tall.  Remove the
     inner portion of the mounting gasket and discard.  Use the outer 
     portion to seal between the plastic base and the duct.  Line up the
     base with the cut out and accurately mark the holes thru the plastic
     duct mount 
     plate.  (see fig 3.)
3.  Revove the humidistat and drill four 3/32” mounting holes.
4.  Place the outer portion of the mounting gaskets on the plastic base
     and mount the base with four screws.  Low voltage wire may enter 
     the humidistat under the gasket.
5.  Connect wires to screw terminals on the control assembly as 
     shown in wiring DIAGRAMS 1-5.  Replace the face and knob.

DUCT MOUNTING ON THE RETURN AIR - DUCT BASE
Humidistat/Dehumidistat versions (recommended)

Do not install the humidistat on the warm air duct or within 48” 
of UV light.
1.  Locate the humidistat at least 24” upstream of the humidifier
     or bypass on the return air duct.  Avoid areas of direct radiation
     like secondary heat exchanger in the fan compartment.
2.  Remove face by inserting screwdriver into the pry slot and
     twisting (see fig. 2)
3.  Use the plastic duct mount plate as a template.  Accurately mark
     and drill the (4) 3/32” mounting holes and cut away the 4-1/4” x 2-1/2”
     section of the duct mount plate.
4.  Place duct mount base gasket on the humidistat base and mount
     the base with four screws.  Low voltage wire may enter the humidistat 
     under the gasket (see fig. 2)
5.  Connect wires to screw terminals on the control assembly as shown in 
     wiring DIAGRAMS 1-5.  Replace face and knob.

MHX3 CALIBRATION INSTRUCTIONS
  (Accurate humidity gauge required)

1.  Use an accurate humidity gauge to determine the current relative
     humidity in the room where the humidstat is located.  This relative
     humidity will be used in step 5.
2.  Remove the face plate from the housing.
3.  Turn the knob on the MHX3 faceplate to the “on” position
4.  Very slowly, turn the knob clockwise until you hear a “click” from
     the humidistat control and leave the knob in this position.
5.  Turn the ring  (not the knob) so that the knob is pointed directly
     at the current relative humidity number determined in STEP 1.
6.  The humidistat in now calibrated to match you humidity gauge.

Reviews: