Setup Check & Setup Modes
(
con tin ued
)
n
The last A2 alarm option to appear on
the display will be the alarm time delay.
If the A1 alarm is activated continuously
for the amount of time specified by this
option the A2 alarm outputs will
activate. The display will indicate the
current A2 alarm time delay in seconds
(figure 18). Press the Mode/Select
switch repeatedly, until the desired A2
alarm time delay (1, 2, 4 or 8 seconds)
appears on the display.
4
is the factory
default for this selection.
Fig ure 18
A1 ALARM OPTIONS
n
Next, the
A1
LED on the front panel
will be flashing while the
Energized/De-energized option is
displayed (figure 19). The display will
indicate the current selection, (
En
or
dE
). Press the Mode/Select switch until
the desired option is displayed.
De-Energized is the factory default for
this selection.
Fig ure 19
n
The
A1
LED on the front panel will be
flashing while the latching/non-latching
option is displayed (figure 20). The
display will indicate the current
selection, (
nL
or
LA
). Press the
Mode/Select switch until the desired
option is displayed. Non-Latching is the
factory default for this selection.