GM9907-L5
bulk scale controller user’s manual
- 51 -
performed
4.7.1
Motor drive feed description
1.
Filling control mode is set as " Motor Drived (1 limit)" mode to control feeding door
ONOFF: Involved I/O Functions are:
Filler Open (Motor) (O21), Filller Close (Motor)
(O22), Filler Gate Closed Pos. (I25)
Take coarse and fine feed process as example:
●
coarse feed process:
(
O21
)
gate open signal output valid,valid time is
“
Feed Gate Open Timer(Co-F)
”
, start coarse feed process.
●
fine feed process
:
When material weight in hopper
≥
Target-Co-Feeding Remains
,
O22
gate close signal output valid
,
valid time is
“
Feed Gate Open Timer(Co-F) -
Feed Gate Open Timer(Fi-F)
”
.
●
Feed close
:
When material weight in hopper
≥
Target-Free fall
,
O22
gate close
signal output valid, till detect Feeding Gate Closed
(
I25
)
.
※
Note
:
If close process timer exceed filler gate close Overtime, controller still
undetect Filler Gate Closed Pos.
(
I25
)
,then controller will stop output Filller Close
signal
(
O22
)
and alarm. After clear alarm
,
continue output the gate close signal.
4.7.2
Motor drive discharge process description
1.
“
DISC Gate Driver Mode
”
set to
“
Normal Motor(One Pos.)
”
to control discharge
:
involved
I/O Function are
:
DISC Gate Open
(
motor
)(
O23
)
, DISC Gate Close
(
motor
)
(O24),
DISC Gate Closed Pos.
(
I27
)
Take discharge process for example
:
●
DISC Gate Open process
:
When discharge process start
,
controller output DISC
Gate Open signal
(
O23
)
to control discharge motor turn to DISC Gate Open way, and
continue set DISC motor gate open signal output timer
,
then DISC Gate Open
(
motor
)
signal
(
O23
)
output.
●
DISC Gate close process
:
When discharge is finished
,
output DISC Gate close
signal
(
O24
)
,to control discharge motor turn to DISC Gate close way, until detect DISC
Gate Closed signal
(
I27
)
input valid then stop output DISC Gate close signal
(
O24
)
,DISC
gate is in close state.
※
Note
:
If DISC Gate close process time exceed set DISC Gate close overtime timer
,
controller still undetect DISC Gate Closed signal
(
I27
)
,then controller will stop
output DISC Gate close signal
(
O24
)
and alarm. After Clear Alarm
,
will continue
output gate close signal.
2.
“
DISC Gate Driver Mode
”
set to
“
Normal Motor(Two Pos.)
”
to control discharge
:
involved