Generac Power Systems TMS200 Specification Download Page 2

Cabinet Specifications

Dimensions

20"W x 10"D x 36"H

Weight

53.8 lbs.

Construction

Single Chamber with Main Door

0.080 14GA Aluminum

UL Type / NEMA 3R Rated

Powder Coat Finish for Corrosion Resistance

UL Listed - Non-Automatic Transfer Switch & Suitable for Service Equipment

Stainless Steel Hardware

3-Point Latching System with Pad-Lockable Handle

Mounting Options

Wall

H-frame

Installed

Pre-wired alarm terminal strip

Electrical Specifications

Voltage/Phase/Amps

120/240 Single-Phase, 200A

120/208 3-Phase, 200A
120/240 3-Phase, 200A

Breaker

Generac 200 amp Utility Breaker

Generac 200 amp Generator Breaker

Fault Current Rating

22k AIC Rated

200A Camlock Generator Connection

Single-Phase: Black L1, Red L2, White-Neutral, Green-Ground

3-Phase: Black L1, Red L2, Blue L3, White-Neutral, Green-Ground

Uses 4 CH E1016 Male Connectors

Mating Connector – CH E1016 Female

Input to Generator

350MCM - #6 AWG

Output to Site

350MCM - #6 AWG

Generator Annunciator Connector

Deutsch DTM04-12PA-L012

Alarm Terminal Board

Generator Run Alarm

Generator Fail – Shutdown Alarm

Generator Fail – Non Shutdown Alarm

Low Fuel Alarm

Generator Theft Alarm

AC Utility Fail Alarm

Additional Components

Mounting Bracket

Installation Mounting Bracket

Alarm Cable

100' length of multi-conductor cable

Enclosure Gasket

Full Exterior x 2"W x 1/2"D Closed Cell Gasket

Shipped loose with switch

2 of 2

 