![Generac Power Systems TMS200 Specification Download Page 2](http://html1.mh-extra.com/html/generac-power-systems/tms200/tms200_specification_2209823002.webp)
Cabinet Specifications
Dimensions
20"W x 10"D x 36"H
Weight
53.8 lbs.
Construction
Single Chamber with Main Door
0.080 14GA Aluminum
UL Type / NEMA 3R Rated
Powder Coat Finish for Corrosion Resistance
UL Listed - Non-Automatic Transfer Switch & Suitable for Service Equipment
Stainless Steel Hardware
3-Point Latching System with Pad-Lockable Handle
Mounting Options
Wall
H-frame
Installed
Pre-wired alarm terminal strip
Electrical Specifications
Voltage/Phase/Amps
120/240 Single-Phase, 200A
120/208 3-Phase, 200A
120/240 3-Phase, 200A
Breaker
Generac 200 amp Utility Breaker
Generac 200 amp Generator Breaker
Fault Current Rating
22k AIC Rated
200A Camlock Generator Connection
Single-Phase: Black L1, Red L2, White-Neutral, Green-Ground
3-Phase: Black L1, Red L2, Blue L3, White-Neutral, Green-Ground
Uses 4 CH E1016 Male Connectors
Mating Connector – CH E1016 Female
Input to Generator
350MCM - #6 AWG
Output to Site
350MCM - #6 AWG
Generator Annunciator Connector
Deutsch DTM04-12PA-L012
Alarm Terminal Board
Generator Run Alarm
Generator Fail – Shutdown Alarm
Generator Fail – Non Shutdown Alarm
Low Fuel Alarm
Generator Theft Alarm
AC Utility Fail Alarm
Additional Components
Mounting Bracket
Installation Mounting Bracket
Alarm Cable
100' length of multi-conductor cable
Enclosure Gasket
Full Exterior x 2"W x 1/2"D Closed Cell Gasket
Shipped loose with switch
2 of 2
Application and Engineering Data
TMS200
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2013 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0195630SBY-E / Printed in U.S.A. 03/13/13
Specification characteristics may change without notice. Dimensions and weights are for preliminary purposes only. Please consult a Generac Power Systems Industrial Dealer for detailed installation drawings.