background image

Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. Please consult a Generac Power Systems Industrial 
Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528 and DIN6271 standards.

POWER RATINGS (kW)

STARTING CAPABILITIES (sKVA)

FUEL

COOLING

COMBUSTION AIR REQUIREMENTS

ENGINE

EXHAUST

STANDBY

PRIME

Single-Phase 120/240VAC @1.0pf

275 kW

Amps: 1146

248 kW

Amps: 1031

Three-Phase 120/208VAC @0.8pf

275 kW

Amps: 954

248 kW

Amps: 859

Three-Phase 120/240VAC @0.8pf

275 kW

Amps: 827

248 kW

Amps: 744

Three-Phase 277/480VAC @0.8pf

275 kW

Amps: 413

248 kW

Amps: 372

Three-Phase 346/600VAC @0.8pf

275 kW

Amps: 331

248 kW

Amps: 298

sKVA vs. Voltage Dip

480VAC

208/240VAC

Alternator

kW

10%

15%

20%

25%

30%

35%

10%

15%

20%

25%

30%

35%

Standard

300

303

454

605

757

908

1059

227

341

454

568

681

794

Upsize 1

350

383

575

767

958

1150

1342

280

410

535

640

770

900

Upsize 2

400

387

581

775

968

1162

1356

345

570

835

1100

1450

1710

Fuel Consumption Rates*

STANDBY

PRIME

Fuel Pump Lift - in (mm)

Percent Load

gph

lph

Percent Load

gph

lph

36 (900)

25%

6.8

25.7

25%

6.2

23.5

50%

11.7

44.2

50%

10.5

39.7

Total Fuel Pump Flow (Comb Return)

75%

15.8

59.8

75%

14.6

55.2

31 gph

100%

19.6

74.2

100%

17.8

67.4

* Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and SCAQMD permitting purposes. 

STANDBY

PRIME

Coolant Flow per Minute

gpm (lpm)

95 (360)

95 (360)

Heat Rejection to Coolant

BTU/hr

722,612

656,250

Inlet Air

 cfm (m3/min)

14,505 (411)

14,505 (411)

Max. Operating Radiator Air Temp

Fº (Cº)

122 (50)

122 (50)

Max. Operating Ambient Temperature

Fº (Cº)

104 (40)

104 (40)

Coolant System Capacity

gal (L)

16.6 (63)

16.6 (63)

Maximum Radiator Backpressure

in H

2

O

1.5

1.5

STANDBY

PRIME

Flow at Rated Power

 cfm (m3/min)

780 (22.09)

702 (19.88)

STANDBY

PRIME

Rated Engine Speed

rpm

1800

1800

Horsepower at Rated kW**

hp

449

396

Piston Speed

 ft/min

1654

1654

BMEP

psi

308

277

** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.

STANDBY

PRIME

Exhaust Flow (Rated Output)

 cfm (m

3

/min) 2050 (58.1)

1845 (52.3)

Max. Backpressure (Post Silencer)

inHg (Kpa)

1.5 (5.1)

1.5 (5.1)

Exhaust Temp (Rated Output)

ºF (ºC)

950 (510)

855 (457)

Exhaust Outlet Size (Open Set)

NPT (male)

101.6 (4)

101.6 (4)

3 of 5

SD275 

operating data (60Hz)

275 kW Diesel

Summary of Contents for SD275

Page 1: ... STANDARDS POWER MATCHED OUTPUT 4 ENGINEERED FOR PERFORMANCE INDUSTRIAL GRADE 4 IMPROVES LONGEVITY AND RELIABILITY Alternator TWO THIRDS PITCH 4 ELIMINATES HARMFUL 3RD HARMONIC LAYER WOUND ROTOR STATOR 4 IMPROVES COOLING CLASS H MATERIALS 4 HEAT TOLERANT DESIGN DIGITAL 3 PHASE VOLTAGE CONTROL 4 FAST AND ACCURATE RESPONSE Controls ENCAPSULATED BOARD W SEALED HARNESS 4 EASY AFFORDABLE REPLACEMENT 4 ...

Page 2: ...tem Oil Filter Type Full Flow System Voltage 24VDC Crankcase Capacity L qts 30 31 68 Battery Charging Alternator Std Battery Size at 0ºC 1155 CCA Battery Group 8D Battery Voltage 2 12VDC Ground Polarity Negative ALTERNATOR SPECIFICATIONS Standard Model 520 mm Generac Voltage Regulator Type Digital Poles 4 Number of Sensed Phases All Field Type Revolving Regulation Accuracy Steady State 0 25 Insula...

Page 3: ...NDBY PRIME Fuel Pump Lift in mm Percent Load gph lph Percent Load gph lph 36 900 25 6 8 25 7 25 6 2 23 5 50 11 7 44 2 50 10 5 39 7 Total Fuel Pump Flow Combustion Return 75 15 8 59 8 75 14 6 55 2 31 gph 100 19 6 74 2 100 17 8 67 4 Refer to Emissions Data Sheet for maximum fuel flow for EPA and SCAQMD permitting purposes STANDBY PRIME Coolant Flow per Minute gpm lpm 95 360 95 360 Heat Rejection to ...

Page 4: ...el Touchscreen na Digital G 200 Paralleling Control Panel Touchscreen na Programmable Crank Limiter Std 21 Light Remote Annunciator Opt Remote Relay Panel 8 or 16 Opt 7 Day Programmable Exerciser Std Special Applications Programmable PLC Std RS 232 Std RS 485 Std All Phase Sensing DVR Std Full System Status Std Utility Monitoring Req H Transfer Switch Std 2 Wire Start Compatible Std Power Output k...

Page 5: ...1 58 120 8936 22 438 181 58 132 9248 35 693 181 58 144 9551 48 946 208 58 147 11195 67 1325 278 58 147 12028 72 1325 278 54 132 10703 Tank Options MDEQ OPT Florida DERM DEP OPT Chicago Fire Code OPT IFC Certification CALL ULC CALL Other Custom Options Available from your Generac Industrial Power Dealer All measurements are approximate and for estimation purposes only Weights are without fuel in ta...

Reviews: