Generac Power Systems RXGW20SHA3 Owner'S Manual Download Page 18

Operation

14

Automatic Transfer Switch Owner’s Manual

Shutting Generator Down To Perform 

Maintenance

Proceed  as  follows  to  shut  down  generator  for  mainte-
nance:

1.

Press OFF button on controller.

2.

Turn main utility disconnect OFF (OPEN).

3.

Turn MLCB (generator disconnect) on generator to

 

OFF  (OPEN)  and  follow  maintenance  proce-
dure(s).

To turn generator back ON:

1.

Turn main utility disconnect ON (CLOSED).

2.

Put generator into AUTO mode.

3.

Set MLCB (generator disconnect) on generator to

 

ON (CLOSED).

The system is now in AUTO mode. 

Testing the SACM

A TEST  pushbutton  is  provided  on  top  of  the  SACM  to 
test  operation  of  load  shed  functions. The TEST  button 
will work when ATS is in utility or generator position. Pro-
ceed as follows to test the SACM:

1.

Turn on utility supply to ATS.

2.

Verify  managed  loads  are  powered  and  all  LEDs 
illuminate on SACM.

3.

Press TEST button on the SACM.

4.

Verify  all  of  the  connected  loads  to  be  “shed”  are

 

disabled.

5.

After  five  minutes,  verify A/C  1  is  energized  and

 

Status LED A/C 1 is ON.

6.

After another 15 seconds, verify A/C 2 is energized 
and Status LED A/C 2 is ON.

7.

After  another  15  seconds,  verify  Load  A/C  3  is 
energized and Status LED Load A/C 3 is ON.

8.

After another 15 seconds, verify A/C 4 is energized 
and Status LED A/C 4 is ON.

Testing The SMM

See  SMM  owner’s/installation  manual  for  testing  proce-
dure.

Fuse Removal and Installation

See 

Figure 3-2

. A fuse removal and installation tool (A) 

is included in the control housing.

Figure 3-2. Fuse Removal and Installation Tool

If  a  fuse  requires  replacement,  snap  tool  free  with  an

 

appropriate  tool  such  as  diagonal  pliers,  and  use  it  to 
replace fuse. The tool can be stored in the control hous-
ing retainer directly above the fuses, with the large thumb

 

tab facing out.
Use  only  Generac  replacement  fuses—part  number 
100000005117, rated 240 VAC, 6.3 Amps, 10,000 AIC. 
Alternative fuses are Littelfuse

®

 021606.3MXHP or Opti-

fuse

®

 FCD-6.3.

10000004183

Rev. A
M1704

A

005450

Summary of Contents for RXGW20SHA3

Page 1: ...el Number RXGW20SHA3 SERIAL NUMBER _________________________ DATE PURCHASED ________________________ WWW GENERAC COM 888 436 3722 Para espa ol visita http www generac com service support product suppo...

Page 2: ...ii Automatic Transfer Switch Owner s Manual 000393a WARNING CANCER AND REPRODUCTIVE HARM www P65Warnings ca gov...

Page 3: ...Manual Operation 11 Close to Utility Source Side 11 Close to Generator Source Side 12 Return to Utility Source Side 12 Voltage Checks 12 Utility Voltage Checks 12 Generator Voltage Checks 12 Generato...

Page 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 5: ...anufacturer does not spe cifically recommend verify that it is safe for others and does not render the equipment unsafe Throughout this publication and on tags and decals affixed to the unit DANGER WA...

Page 6: ...warning could result in death or serious injury WARNING Equipment damage This unit is not intended for use as a prime power source It is intended for use as an intermediate power supply in the event...

Page 7: ...ements could result in death serious injury and equipment or property damage 000120 CAUTION Equipment damage Verify all conductors are tightened to the factory specified torque value Failure to do so...

Page 8: ...Safety Rules General Information 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 9: ...Install transfer switch as close as possible to electrical loads that will be connected to it Mount transfer switch vertically to a rigid supporting structure Level all mount ing points to prevent tr...

Page 10: ...Generator Power Supply Installation and interconnection diagrams are provided in this manual NOTE All installations must comply with national state and local codes It is the responsibility of the ins...

Page 11: ...used apply corrosion inhibitor to conductors After tightening terminal lugs carefully wipe away any excess corrosion inhibitor Tighten terminal lugs to required torque values as noted on decal locate...

Page 12: ...4 12V N1 N2 T1 Replace with Littlefuse 021606 3MXHP Generac 10000005117 250 vac 6 3A 23TRANSFER 1 1 1 1 2 2 2 2 J T1 N2 0 194 23A N1 004435 A Thermostat 1 B Air conditioner 1 C Thermostat 2 D Air cond...

Page 13: ...ch manual operating handle The 2017 NEC requires the short circuit current rating of the trans fer equipment based on type of overcurrent protective device protecting transfer equipment be field marke...

Page 14: ...Installation 10 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 15: ...g narrow slot in the inside cover The top of the movable contact carrier arm is yellow to be easily identified Manual operation handle in UP position LOAD terminals T1 T2 are connected to util ity ter...

Page 16: ...art 2 Allow generator to stabilize and warm up at no load for at least five minutes 3 Set generator s main circuit breaker CB1 to ON CLOSED 4 Verify no load voltage and frequency with an accurate AC v...

Page 17: ...when utility source power is turned off after a five second delay factory default setting After starting transfer switch should connect load circuits to standby side after a five second delay Allow sy...

Page 18: ...M 4 Verify all of the connected loads to be shed are disabled 5 After five minutes verify A C 1 is energized and Status LED A C 1 is ON 6 After another 15 seconds verify A C 2 is energized and Status...

Page 19: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 15 Section 4 Drawings and Diagrams Installation Drawing No 10000047450...

Page 20: ...Drawings and Diagrams 16 Automatic Transfer Switch Owner s Manual Interconnection Drawing No 10000047283 Page 1 of 4 Liquid Cooled Engine Generator...

Page 21: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 17 No 10000047283 Page 2 of 4 Liquid Cooled Engine Generator...

Page 22: ...Drawings and Diagrams 18 Automatic Transfer Switch Owner s Manual No 10000047283 Page 3 of 4 Air Cooled Engine Generator...

Page 23: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 19 No 10000047283 Page 4 of 4 Air Cooled Engine Generator...

Page 24: ...Drawings and Diagrams 20 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 25: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 21 This page intentionally left blank...

Page 26: ...Drawings and Diagrams 22 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 27: ......

Page 28: ...ights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290...

Reviews: