Installation

Automatic Transfer Switch Owner’s Manual

7

Section 3:  Installation

Introduction

This equipment has been wired and tested at the factory.

Installing the switch includes the following procedures:

Mounting the enclosure.

Connecting power source and load leads.

Connecting the generator start and sensing circuit.

Connecting any auxiliary contact (if needed).

Testing functions.

Mounting

Mounting dimensions for the transfer switch enclosure

are in this manual. Enclosures are typically wall-

mounted. Se

Drawings and Diagrams

.

This transfer switch is mounted in a UL type 3R

enclosure. It can be mounted outside or inside and

should be based on the layout of installation,

convenience and proximity to the utility supply and load

center.

Install the transfer switch as close as possible to the

electrical loads that are to be connected to it. Mount the

switch vertically to a rigid supporting structure. To prevent

switch distortion, level all mounting points. If necessary,

use washers behind mounting holes to level the unit.

Connecting Power Source and Load Lines

Installation and interconnection diagrams are provided in

this manual. 

NOTE: 

All installations must comply with national, state 

and local codes. It is the responsibility of the installer to 
perform an installation that will pass the final electrical 
inspection.

The utility supply connection is made at the utility service

disconnect circuit breaker terminals. The generator and

customer load connections are made at the transfer

switch mechanism, inside the switch enclosure.

Conductor sizes must be adequate to handle the

maximum current to which they will be subjected, based

on the American Wire Gauge (AWG) 167°F (75°C)

column of tables, charts, etc. used to size conductors.

The installation must comply fully with all applicable

codes, standards and regulations.

All power cables can enter the enclosure through the

knockouts provided. If not using the knockouts, conduit

entry into the enclosure above the level of uninsulated

live parts shall use fittings listed for use in wet locations

to maintain the Type 3R rating. Conduits should be

arranged to provide separation between the Utility and

Generator supply conductors inside the enclosure.

NOTE: 

If aluminum conductors are used, apply corrosion 

inhibitor to conductors. After tightening terminal lugs, 
carefully wipe away any excess corrosion inhibitor.

Tighten terminal lugs to the torque values as noted on the

decal located on the inside of the door. After tightening

terminal lugs, carefully wipe away any excess corrosion

inhibitor. 

Connect power source and load conductors to clearly

marked terminal lugs on transfer mechanism as follows:

1.

Connect utility (normal) power source cables to

utility service disconnect circuit breaker.

2.

Connect the generator (standby) source power

cables to transfer switch terminals E1, E2., and E3

3.

Connect customer LOAD leads to switch terminals

T1, T2, and T3.

Connecting Start Circuit Wires

Control system interconnections may consist of N1, N2,

and T1, and leads 23 and 194. The generator control

wiring is a Class 1 signaling circuit. Reference the

Installation Manual of the specific generator for wiring

connection details. Recommended wire gauge sizes for

this wiring depends on the length of the wire, as

recommended in the following chart:

 

Exception: 

Conductors of AC and DC circuits, rated

1000 volts nominal or less, shall be permitted to occupy

the same equipment, cable, or conduit. All conductors

shall have an insulation rating equal to at least the

maximum circuit voltage applied to any conductor within

the equipment, cable, or conduit. See NEC 300.3(C)(1).

NOTE: 

 An RTS series transfer switch without a T1/

Fused connection must use a 120VAC protected circuit

from the panel board to power the battery charge circuit

(dedicated 15/20 amp circuit). 

(000119)

Equipment malfunction. Installing a dirty or damaged
transfer switch will cause equipment malfunction and 
will result in death or serious injury. 

DANGER

Electrocution. Turn utility and emergency
power supplies to OFF before connecting 
power source and load lines. Failure to do so 
will result in death or serious injury.

 

(000116)

DANGER

Maximum Wire Length

Recommended Wire Size

1–115 ft (1–35 m)

No. 18 AWG

116–185 ft (36–56 m)

No. 16 AWG

186–295 ft (57–89 m)

No. 14 AWG

296–460 ft (90–140 m)

No. 12 AWG

(000120)

CAUTION

Equipment damage. Verify all conductors are 
tightened to the factory specified torque value. 
Failure to do so could result in damage 
to the switch base.

 

Summary of Contents for RTSW100G3

Page 1: ...TSW100K3 RTSW200G3 RTSW200J3 RTSW200K3 MODEL NUMBER _________________________ SERIAL NUMBER _________________________ DATE PURCHASED ________________________ WWW GENERAC COM 1 888 GENERAC 1 888 436 37...

Page 2: ...contains or emits chemicals known to the state of California to cause cancer birth defects and other reproductive harm 000004 WARNING California Proposition 65 Engine exhaust and some of its constitue...

Page 3: ...Normal Source Side 9 Voltage Checks 10 Utility Voltage Checks 10 Generator Voltage Checks 10 Generator Tests Under Load 11 Checking Automatic Operation 11 Installation Summary 11 Shutting Generator Do...

Page 4: ...Table of Contents iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 5: ...THIS MANUAL AT ANY TIME Safety Rules The manufacturer cannot anticipate every possible circumstance that might involve a hazard The warnings in this manual and on tags and decals affixed to the unit...

Page 6: ...r serious injury 000157 DANGER Electrocution Do not disable or modify the connection box door safety switch Doing so will result in death or serious injury Automatic start up Disconnect utility power...

Page 7: ...Health Administration OSHA have established Never handle any kind of electrical device while standing in water while barefoot or while hands or feet are wet DANGEROUS ELECTRICAL SHOCK MAY RESULT Beca...

Page 8: ...Introduction and Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 9: ...nsfer switch prevents electrical feedback between two different power sources such as the UTILITY and GENERATOR sources and for that reason codes require it in all standby electric system installation...

Page 10: ...ssociation NEMA and UL 3R type UL and NEMA 3R indoor outdoor rated type enclosures primarily provide a degree of protection against falling rain and sleet and are undamaged by the formation of ice on...

Page 11: ...ion between the Utility and Generator supply conductors inside the enclosure NOTE If aluminum conductors are used apply corrosion inhibitor to conductors After tightening terminal lugs carefully wipe...

Page 12: ...xiliary Contacts are rated 10 amps at 125 or 250 volts AC Figure 3 1 Auxiliary Contacts Switch Position Utility Standby Common to Normally Open Open Closed Common to Normally Closed Closed Open 000134...

Page 13: ...Close to Normal Source Side Before proceeding verify the position of the switch by observing Window A in Figure 4 1 If Window A reads ON the contacts are closed in the normal position no further acti...

Page 14: ...ltage and frequency Measure across ATS terminal lugs E1 to E2 E2 to E3 E1 to NEUTRAL E2 to NEUTRAL and E3 to NEUTRAL Frequency should be 60 62 Hz 5 When certain that Three Phase Rotation is correct an...

Page 15: ...circuit breaker The utility power source now powers the loads 9 The system is now set for fully automatic operation Checking Automatic Operation To check the system for proper automatic operation pro...

Page 16: ...Operation 12 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 17: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 13 Section 5 Drawings and Diagrams Installation Drawing 100 200A Three Phase Drawing 0L2826 001254...

Page 18: ...Drawings and Diagrams 14 Automatic Transfer Switch Owner s Manual Interconnection Drawing 100 200A RTS Series Three Phase Drawing 0L2828 Sheet 1 of 2 001256...

Page 19: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 15 Interconnection Drawing 100 200A RTS Series Three Phase Drawing 0L2828 Sheet 2 of 2 001260...

Page 20: ...2 FUSE 5A SENSING 1 ALL CONTACTS SHOWN WITH TRANSFER SWITCH IN UTILITY POSITION B2 A2 ATS TRANSFER SWITCH CONTACTOR C CONTACTOR ACTUATING COIL N2A LEGEND TR E1 4 6 N2A 205 LS2 WHITE C RED LS3 LS1 A1 B...

Page 21: ...N1B N2A 3 N1A N3 5 6 1 PM 2 N1A 8 7 N1B TR 126 A1 B2 A2 B1 F2 N2 N1 F1 23 194 205 194 205 E1 T2 E2 T1 T1 E1 T2 E2 N1B N2A ATS N2A N1B N1 N2 NB N3 N3 N3 UCB GND N1B N2A N2A N2A N1B 23 E1 N2A N1B NOTE B...

Page 22: ...2 FUSE 5A SENSING 1 ALL CONTACTS SHOWN WITH TRANSFER SWITCH IN UTILITY POSITION B2 A2 ATS TRANSFER SWITCH CONTACTOR C CONTACTOR ACTUATING COIL N2A LEGEND TR E1 4 6 N2A 205 LS2 WHITE C RED LS3 LS1 A1 B...

Page 23: ...N1B N2A 3 N1A N3 5 6 1 PM 2 N1A 8 7 N1B TR 126 A1 B2 A2 B1 F2 N2 N1 F1 23 194 205 194 205 E1 T2 E2 T1 T1 E1 T2 E2 N1B N2A ATS N2A N1B N1 N2 NB N3 N3 N3 UCB GND N1B N2A N2A N2A N1B 23 E1 N2A N1B NOTE B...

Page 24: ...TACTS SHOWN WITH TRANSFER SWITCH IN UTILITY POSITION 240V E1A E2A B2 A2 ATS TRANSFER SWITCH CONTACTOR C CONTACTOR ACTUATING COIL N2B LEGEND TR E1A 4 6 N2B 205 LS2 WHITE C RED LS3 LS1 A1 B1 T1 126 126...

Page 25: ...N1B TR 126 A1 B2 A2 B1 F2 N2 N1 F1 23 194 E1A 205 194 N2B N2B E2A 205 N1B N1B E1 T2 E2A T1 T1 E1 E2 T2 E2 N1A N2A ATS N2A N1A N1 N2 X4 H1 E1A NB N3 E2A X1 H4 H1 X4 N1B E1 N2B N2B N3 N1B E2 X1 H4 N3 N...

Page 26: ...Drawings and Diagrams 22 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Page 27: ......

Page 28: ...c All rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ......

Reviews: